{"product_id":"900h02-0001-honeywell-do-16-channel-24vdc-pwa-hc900-controller","title":"900H02-0001 | Honeywell DO 16 Channel 24vdc Pwa HC900 Controller","description":"\u003ch3\u003eProduct Overview\u003c\/h3\u003e\n\u003cp\u003eThe \u003cstrong\u003eHoneywell 900H02-0001\u003c\/strong\u003e is a \u003cstrong\u003e16-Channel DC Digital Output Module\u003c\/strong\u003e (sinking type) for the Honeywell \u003cstrong\u003eControlEdge HC900\u003c\/strong\u003e hybrid controller platform. It provides \u003cstrong\u003elow-side switching (current sinking)\u003c\/strong\u003e outputs organized into \u003cstrong\u003etwo galvanically isolated groups of 8 channels\u003c\/strong\u003e each, enabling precise control of field devices such as solenoid valves, motor contactors, pilot lights, and alarm indicators in industrial automation and process control systems.\u003c\/p\u003e\n\u003ch3\u003eKey Specifications\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eModel Number:\u003c\/strong\u003e 900H02-0001\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eSeries:\u003c\/strong\u003e Honeywell ControlEdge HC900\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eProduct Type:\u003c\/strong\u003e 16-Channel Digital Output Module — DC Sinking Type\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eOutput Channels:\u003c\/strong\u003e \u003cstrong\u003e16 outputs\u003c\/strong\u003e (2 groups of 8 channels)\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eOutput Type:\u003c\/strong\u003e \u003cstrong\u003eIntelligent Power Switch (IPS)\u003c\/strong\u003e, low-side switching (current sinking)\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eOperating Voltage:\u003c\/strong\u003e \u003cstrong\u003e6.5 – 32 VDC\u003c\/strong\u003e (5.0 – 6.5 VDC @ \u0026lt; 0.5 A per channel)\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003ePeak Voltage:\u003c\/strong\u003e \u003cstrong\u003e34 VDC\u003c\/strong\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eMaximum Load Current:\u003c\/strong\u003e \u003cstrong\u003e1 A per point\u003c\/strong\u003e, \u003cstrong\u003e8 A max per module\u003c\/strong\u003e (resistive load)\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eLamp Load:\u003c\/strong\u003e \u003cstrong\u003e0.5 A per point\u003c\/strong\u003e (incandescent, 5 mH max)\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eON Voltage Drop:\u003c\/strong\u003e \u003cstrong\u003e0.3 VDC @ 1 A\u003c\/strong\u003e load\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eMaximum Leakage Current:\u003c\/strong\u003e ≤ \u003cstrong\u003e0.15 mA\u003c\/strong\u003e @ 32 VDC\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eMaximum Inrush Current:\u003c\/strong\u003e \u003cstrong\u003e4 A for 10 ms\u003c\/strong\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eResponse Time:\u003c\/strong\u003e \u003cstrong\u003e6 ms\u003c\/strong\u003e (OFF to ON) \/ \u003cstrong\u003e6 ms\u003c\/strong\u003e (ON to OFF)\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eGalvanic Isolation:\u003c\/strong\u003e 2 groups of 8 outputs, isolated from chassis and between groups\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eOverload Protection:\u003c\/strong\u003e Electronic high current and high temperature limiting; resets after cycling field power\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003ePower Supply Loading:\u003c\/strong\u003e 5V: \u003cstrong\u003e340 mA\u003c\/strong\u003e; 24V: \u003cstrong\u003e0 mA\u003c\/strong\u003e (externally powered)\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eDimensions (H × W × D):\u003c\/strong\u003e \u003cstrong\u003e137 × 35.6 × 137.16 mm\u003c\/strong\u003e (5.4\" × 1.4\" × 5.4\")\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eWeight:\u003c\/strong\u003e \u003cstrong\u003e0.35 lbs\u003c\/strong\u003e (159g)\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eOperating Temperature:\u003c\/strong\u003e \u003cstrong\u003e0°C to +60°C\u003c\/strong\u003e (32°F to 140°F)\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eHumidity:\u003c\/strong\u003e 5% to 95% non-condensing\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eCertifications:\u003c\/strong\u003e \u003cstrong\u003eCE\u003c\/strong\u003e; Class I, Div. 2, Groups A–D, T4; Class I, Zone 2\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eStatus:\u003c\/strong\u003e \u003cstrong\u003eDiscontinued by Manufacturer\u003c\/strong\u003e — replaced by 900H02-0202 series\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eCore Features\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003e16-channel high-density\u003c\/strong\u003e digital output in compact single-slot form factor\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eLow-side switching (sinking)\u003c\/strong\u003e design for flexible field device integration\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eTwo isolated groups of 8 channels\u003c\/strong\u003e — each group has independent +V and COM screw terminals\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eIntelligent Power Switch (IPS)\u003c\/strong\u003e technology with built-in overload and thermal protection\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eIndividual green LED\u003c\/strong\u003e for each channel indicating ON\/OFF state\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eStatus LEDs:\u003c\/strong\u003e Green blinking = module scanning; Amber blinking = channels forced; Red = module diagnostics\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eHot-swappable\u003c\/strong\u003e — module can be removed\/inserted under controller power for maintenance\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eElectronic overload protection\u003c\/strong\u003e — auto-recovery after field power cycle\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eGalvanic isolation\u003c\/strong\u003e simplifies installation and eliminates need for external isolation hardware\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eApplications\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eSolenoid valve control in process loops\u003c\/li\u003e\n\u003cli\u003eMotor starter and contactor triggering\u003c\/li\u003e\n\u003cli\u003ePilot light and indicator lamp control\u003c\/li\u003e\n\u003cli\u003eAlarm siren and beacon activation\u003c\/li\u003e\n\u003cli\u003eRelay logic interfacing with legacy control systems\u003c\/li\u003e\n\u003cli\u003eMaterial handling and conveyor control\u003c\/li\u003e\n\u003cli\u003eWater treatment and wastewater systems\u003c\/li\u003e\n\u003cli\u003eBurner management and combustion control\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eFAQ\u003c\/h3\u003e\n\u003cp\u003e\u003cstrong\u003eQ: What is the difference between 900H02-0001 and 900H02-0202?\u003c\/strong\u003e\u003cbr\u003eA: The 900H02-0001 is the \u003cstrong\u003eearly production revision\u003c\/strong\u003e of the 16-channel DC digital output module. Honeywell has since transitioned to the \u003cstrong\u003e900H02-0202\u003c\/strong\u003e and later suffix variants (e.g., 900H02-0302). Functionally, all variants provide identical 16-channel DC sinking output capability. The 900H02-0001 is discontinued but remains fully compatible with HC900 systems.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: How do I reset an overloaded channel?\u003c\/strong\u003e\u003cbr\u003eA: The 900H02-0001 features \u003cstrong\u003eelectronic overload protection\u003c\/strong\u003e with automatic current and temperature limiting. To reset a tripped overload, \u003cstrong\u003ecycle the external field power\u003c\/strong\u003e (turn OFF, then ON). The module does not require fuse replacement.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: Can I mix different voltages in the two output groups?\u003c\/strong\u003e\u003cbr\u003eA: \u003cstrong\u003eYes.\u003c\/strong\u003e The two groups of 8 channels are \u003cstrong\u003egalvanically isolated\u003c\/strong\u003e from each other, allowing each group to operate at different field supply voltages (within the 6.5–32 VDC range).\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: What does the red LED indicate?\u003c\/strong\u003e\u003cbr\u003eA: A \u003cstrong\u003ered status LED\u003c\/strong\u003e indicates a module diagnostic failure or internal hardware fault. Refer to the HC900 Designer software for detailed diagnostic information.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: Is this module hot-swappable?\u003c\/strong\u003e\u003cbr\u003eA: \u003cstrong\u003eYes.\u003c\/strong\u003e The ControlEdge HC900 platform supports \u003cstrong\u003eremoval and insertion of I\/O modules under power\u003c\/strong\u003e (RIUP). However, field power to the specific module should be disconnected before removal to prevent arcing.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: What is the maximum total current for the module?\u003c\/strong\u003e\u003cbr\u003eA: The maximum total current is \u003cstrong\u003e8 A per module\u003c\/strong\u003e (sum of all 16 channels). Individual channels are rated for 1 A each (resistive load) or 0.5 A (incandescent lamp load).\u003c\/p\u003e\n\u003ch3\u003eInstallation Guide\u003c\/h3\u003e\n\u003col\u003e\n\u003cli\u003e\n\u003cstrong\u003ePower down field power\u003c\/strong\u003e to the module before installation (controller power may remain ON for RIUP).\u003c\/li\u003e\n\u003cli\u003eInsert the 900H02-0001 into any available I\/O slot in the HC900 rack.\u003c\/li\u003e\n\u003cli\u003eConnect \u003cstrong\u003eexternal field power\u003c\/strong\u003e (+V and COM) to the screw terminals for each group of 8 channels.\u003c\/li\u003e\n\u003cli\u003eWire field devices (solenoids, relays, lamps) to the appropriate output channels.\u003c\/li\u003e\n\u003cli\u003eVerify all connections and apply field power.\u003c\/li\u003e\n\u003cli\u003eCheck LED indicators — green blinking status LED confirms module scanning.\u003c\/li\u003e\n\u003cli\u003eConfigure output channels via \u003cstrong\u003eHoneywell HC Designer\u003c\/strong\u003e software.\u003c\/li\u003e\n\u003c\/ol\u003e\n\u003ch3\u003eSelection Tips\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eVerify load type:\u003c\/strong\u003e Ensure your field devices require \u003cstrong\u003esinking (low-side)\u003c\/strong\u003e switching. For sourcing applications, consider the 900H32 series (32-channel DC sourcing output module).\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eCalculate total current:\u003c\/strong\u003e Do not exceed \u003cstrong\u003e8 A total per module\u003c\/strong\u003e. For higher current requirements, distribute loads across multiple modules.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eCheck voltage range:\u003c\/strong\u003e Confirm field power stays within \u003cstrong\u003e6.5 – 32 VDC\u003c\/strong\u003e. For AC output applications, consider 900H03 (120\/240 VAC) or 900H01 (relay output) modules.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eFor new designs:\u003c\/strong\u003e Consider ordering \u003cstrong\u003e900H02-0202\u003c\/strong\u003e or later revision for manufacturer warranty and support coverage.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eTerminal blocks:\u003c\/strong\u003e Use compatible terminal blocks — \u003cstrong\u003e900TEK-0200\u003c\/strong\u003e (Euro style, 20-position) or \u003cstrong\u003e900TBK-0200\u003c\/strong\u003e (Barrier style, 20-position). For high-density applications, \u003cstrong\u003e900TCK-0200\u003c\/strong\u003e (36-terminal Euro style) may be required.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eEnvironmental:\u003c\/strong\u003e Use an appropriate enclosure if deploying in dusty, wet, or corrosive environments. Operating temperature is 0°C to +60°C.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eCompatible Products\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eControllers:\u003c\/strong\u003e HC900 C30 (900C32), C50 (900C52), C70\/C75 (900C72\/900C75)\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eRacks:\u003c\/strong\u003e 900R04, 900R08, 900R12 (with redundant power options: 900R08R, 900R12R)\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003ePower Supplies:\u003c\/strong\u003e 900P01 (120\/240 VAC), 900P24 (24 VDC)\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eTerminal Blocks:\u003c\/strong\u003e 900TEK-0200 (Euro), 900TBK-0200 (Barrier), 900TCK-0200 (High-Density Euro)\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eReplacement Module:\u003c\/strong\u003e 900H02-0202 (current production version)\u003c\/li\u003e\n\u003c\/ul\u003e","brand":"Honeywell","offers":[{"title":"Default Title","offer_id":53827345612984,"sku":"900H02-0001","price":99.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0935\/6132\/3704\/files\/900H02-0001r180.png?v=1785223061","url":"https:\/\/www.globalpetroparts.com\/products\/900h02-0001-honeywell-do-16-channel-24vdc-pwa-hc900-controller","provider":"Global Petro Parts Automation","version":"1.0","type":"link"}