{"product_id":"allen-bradley-1756-if16ihk-controllogix-analog-input-module","title":"Allen-Bradley 1756-IF16IHK ControlLogix Analog Input Module","description":"\u003cp\u003eConfigured for high-density analog signal processing in ControlLogix system platforms, the \u003cstrong\u003eAllen-Bradley 1756-IF16IHK\u003c\/strong\u003e (\u003cstrong\u003e1756-IF16IHK\u003c\/strong\u003e) Analog Input Module provides direct physical\/electrical execution of current loop measurements. This module supports 16 independent input channels, facilitating high-resolution data acquisition from 0-20 mA and 4-20 mA field transmitters while maintaining isolated signal integrity across the backplane.\u003c\/p\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003e1756-IF16IHK\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eAllen-Bradley\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrigin\u003c\/td\u003e\n\u003ctd\u003eUSA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.45 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003eSingle-slot ControlLogix module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003e0 to 60 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003e5.30 W\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Channels\u003c\/td\u003e\n\u003ctd\u003e16\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCurrent Range\u003c\/td\u003e\n\u003ctd\u003e0-20 mA \/ 4-20 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eResolution\u003c\/td\u003e\n\u003ctd\u003e16-21 bits\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eIsolation Voltage\u003c\/td\u003e\n\u003ctd\u003e250 V Continuous\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eIndustrial Control Deterministic Network Connectivity\u003c\/h3\u003e\n\u003cp\u003eThe 1756-IF16IHK is engineered to interface with 4-20 mA HART loop protocols, enabling advanced diagnostic data extraction from intelligent field devices. The module maintains high backplane bus communication velocity, ensuring that process variables are updated synchronously with the controller scan cycle. Firmware flash compatibility is mandatory to support updated HART command libraries and diagnostic features. Furthermore, the module's 16-channel architecture allows for efficient I\/O density scaling within a single chassis, provided that the 5.1 VDC and 24 VDC backplane current consumption does not exceed the power supply design limits.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions (FAQ)\u003c\/h3\u003e\n\u003cp\u003eQ: Can this module be hot-swapped while the ControlLogix chassis is powered?\u003c\/p\u003e\n\u003cp\u003eA: Yes, the 1756-IF16IHK supports removal and insertion under power (RIUP). However, ensure field-side wiring is disconnected from the Removable Terminal Block (RTB) to prevent potential shorts or electrical transients on the input circuits during module replacement.\u003c\/p\u003e\n\u003cp\u003eQ: Is channel-to-channel isolation provided for all 16 inputs?\u003c\/p\u003e\n\u003cp\u003eA: The module is designed with 250 V continuous isolation to protect against ground potential differences. Always verify the grounding strategy for the specific 4-20 mA loop to prevent ground loops across the isolation barrier.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eRTB Termination:\u003c\/strong\u003e Use the compatible Removable Terminal Block (RTB) for all field wiring. Ensure wires are stripped to the appropriate length and torqued to manufacturer specifications to maintain connection stability.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eShielding and Grounding:\u003c\/strong\u003e Terminate all cable shields to a common earth ground at the signal source or the chassis ground bar. Avoid multiple ground points, which can introduce noise into the sensitive 250-ohm input impedance circuits.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eVoltage Protection:\u003c\/strong\u003e The module features 28.8 VDC input overvoltage protection. Ensure that field wiring does not exceed this limit, as excessive voltage may permanently damage the input circuitry.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eCable Routing:\u003c\/strong\u003e Segregate analog signal cabling from high-voltage AC power lines and VFD output leads. Maintain a minimum distance of 300 mm from potential sources of EMI to ensure signal precision and prevent HART communication timeouts.\u003c\/li\u003e\n\u003c\/ul\u003e","brand":"Allen Bradley","offers":[{"title":"Default Title","offer_id":53546621927608,"sku":"1756-IF16IHK","price":99.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0935\/6132\/3704\/files\/1756SC-IF8H_eb7b9baf-2477-4f9e-8a55-8616e3a8cc77.jpg?v=1780567173","url":"https:\/\/www.globalpetroparts.com\/products\/allen-bradley-1756-if16ihk-controllogix-analog-input-module","provider":"Global Petro Parts Automation","version":"1.0","type":"link"}