{"product_id":"honeywell-cc-paih02-hart-analog-input-module","title":"Honeywell CC-PAIH02 HART Analog Input Module","description":"\u003ch3\u003eOverview\u003c\/h3\u003e\n\u003cp\u003eThe \u003cstrong\u003eHoneywell CC-PAIH02\u003c\/strong\u003e (part number 51405038-375) is a \u003cstrong\u003e16-Channel HART Analog Input Module\u003c\/strong\u003e for Honeywell Experion™ PKS Series C distributed control systems. It accepts current and voltage inputs with full HART communication capability, enabling remote device diagnostics and multivariable instrument integration.\u003c\/p\u003e\n\u003ch3\u003eTechnical Specifications\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eManufacturer:\u003c\/strong\u003e Honeywell\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eModel:\u003c\/strong\u003e CC-PAIH02\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003ePart Number:\u003c\/strong\u003e 51405038-375\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eType:\u003c\/strong\u003e 16-Channel HART Analog Input Module\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eInput Channels:\u003c\/strong\u003e 16 (12 single-ended \/ 4 differential)\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eInput Types:\u003c\/strong\u003e Voltage, current (2-wire or self-powered transmitters)\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eInput Ranges:\u003c\/strong\u003e 0–5 V, 1–5 V, 0.4–2 V, 4–20 mA (through 250 Ω)\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eA\/D Resolution:\u003c\/strong\u003e 16 bits (majority of sources); 12–16 bits (some sources)\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eHART Protocol:\u003c\/strong\u003e HART 5\/7 (multivariable capable)\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eCommon Mode Rejection Ratio (CMRR):\u003c\/strong\u003e 70 dB (DC to 60 Hz, 500 Ω imbalance)\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eCommon Mode Voltage:\u003c\/strong\u003e −6 to +5 V peak (DC to 60 Hz)\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eNormal Mode Rejection Ratio (NMRR):\u003c\/strong\u003e 19 dB (at 60 Hz)\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eNormal Mode Filter:\u003c\/strong\u003e Single-pole RC, −3 dB @ 6.5 Hz\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eMaximum Normal Mode Input:\u003c\/strong\u003e ±30 V (differential, no damage)\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eCrosstalk:\u003c\/strong\u003e −60 dB (DC to 60 Hz, channel-to-channel)\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eInput Impedance (voltage):\u003c\/strong\u003e \u0026gt;10 MΩ\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eInput Scan Rate:\u003c\/strong\u003e 50 ms\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eHardware Accuracy:\u003c\/strong\u003e ±0.075 % FS (23.5 °C ± 2 °C); ±0.15 % FS (0–60 °C)\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003ePower Consumption:\u003c\/strong\u003e 60 W max\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eWeight:\u003c\/strong\u003e 0.54 kg (1.20 lb)\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eEnvironmental \u0026amp; Safety Ratings\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eOperating Temperature:\u003c\/strong\u003e 0 °C to +60 °C\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eStorage Temperature:\u003c\/strong\u003e −40 °C to +70 °C\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eHumidity:\u003c\/strong\u003e 5 % – 95 % RH non-condensing\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eCoating:\u003c\/strong\u003e G3 environmental coating\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eCompliance:\u003c\/strong\u003e CE, UL, CSA, RoHS\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eKey Features\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e16-channel HART analog input for smart transmitter integration\u003c\/li\u003e\n\u003cli\u003eFull HART 5\/7 protocol support for remote diagnostics and configuration\u003c\/li\u003e\n\u003cli\u003eMultivariable capability for advanced device data retrieval\u003c\/li\u003e\n\u003cli\u003e16-bit resolution for precise signal conversion\u003c\/li\u003e\n\u003cli\u003eOpen-wire detection and bad PV identification\u003c\/li\u003e\n\u003cli\u003eOptional redundancy for fault-tolerant operation\u003c\/li\u003e\n\u003cli\u003eNon-incendive field power for hazardous area transmitters\u003c\/li\u003e\n\u003cli\u003eSupersedes older CC-PAIH01 module\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eFAQ\u003c\/h3\u003e\n\u003cp\u003e\u003cstrong\u003eQ: What is the difference between CC-PAIH01 and CC-PAIH02?\u003c\/strong\u003e\u003cbr\u003eA\u0026gt; CC-PAIH02 supersedes CC-PAIH01. CC-PAIH02 supports differential inputs on \u003cstrong\u003eall 16 channels\u003c\/strong\u003e; CC-PAIH01 only supports differential on channels 13–16. CC-PAIH02 also offers enhanced HART processing.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: Does every channel support HART?\u003c\/strong\u003e\u003cbr\u003eA\u0026gt; Yes, all 16 channels are HART-enabled for communication with smart transmitters and multivariable instruments.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: What is the maximum power consumption?\u003c\/strong\u003e\u003cbr\u003eA\u0026gt; Maximum power consumption is 60 W under full load conditions.\u003c\/p\u003e\n\u003ch3\u003eInstallation Guidelines\u003c\/h3\u003e\n\u003col\u003e\n\u003cli\u003eMount the CC-PAIH02 on the appropriate IOTA base (CC-TAIX01, CC-TAIX11, etc.).\u003c\/li\u003e\n\u003cli\u003eConnect 4–20 mA field wiring with shielded twisted-pair cable.\u003c\/li\u003e\n\u003cli\u003eVerify HART device communication via Experion PKS Device Manager.\u003c\/li\u003e\n\u003cli\u003eConfigure input range, scaling, and HART parameters via Control Builder.\u003c\/li\u003e\n\u003c\/ol\u003e\n\u003ch3\u003eSelection Tips\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eChoose CC-PAIH02 for HART-enabled analog input applications requiring remote device diagnostics.\u003c\/li\u003e\n\u003cli\u003eFor non-HART applications, consider CC-PAIX02 to reduce cost.\u003c\/li\u003e\n\u003cli\u003eVerify your transmitters support HART protocol before ordering.\u003c\/li\u003e\n\u003c\/ul\u003e","brand":"Honeywell","offers":[{"title":"Default Title","offer_id":53862476251320,"sku":"CC-PAIH02","price":166.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0935\/6132\/3704\/files\/CC-PAIH02_2.png?v=1785909901","url":"https:\/\/www.globalpetroparts.com\/products\/honeywell-cc-paih02-hart-analog-input-module","provider":"Global Petro Parts Automation","version":"1.0","type":"link"}