{"product_id":"honeywell-cc-pdis01-digital-input-sequence-of-events","title":"Honeywell CC-PDIS01 Digital Input Sequence of Events","description":"\u003ch3\u003eOverview\u003c\/h3\u003e\n\u003cp\u003eThe \u003cstrong\u003eHoneywell CC-PDIS01\u003c\/strong\u003e (part number 51405042-175\/176) is a \u003cstrong\u003e32-Channel Digital Input Sequence of Events (DISOE) Module\u003c\/strong\u003e for Honeywell Experion™ PKS Series C distributed control systems. It captures discrete input state changes with 1 ms timestamp resolution, enabling precise event sequencing for safety diagnostics and root-cause analysis.\u003c\/p\u003e\n\u003ch3\u003eTechnical Specifications\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eManufacturer:\u003c\/strong\u003e Honeywell\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eModel:\u003c\/strong\u003e CC-PDIS01\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003ePart Number:\u003c\/strong\u003e 51405042-175 \/ 51405042-176\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eType:\u003c\/strong\u003e 32-Channel Digital Input Sequence of Events (DISOE)\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eInput Channels:\u003c\/strong\u003e 32\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eInput Voltage Range:\u003c\/strong\u003e 18–30 VDC\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eON Sense Voltage\/Current:\u003c\/strong\u003e ≥13 VDC or ≥3 mA\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eOFF Sense Voltage\/Current:\u003c\/strong\u003e ≤5 VDC or ≤1.2 mA\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eInput Impedance:\u003c\/strong\u003e 4.2 kΩ\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eSOE Resolution:\u003c\/strong\u003e 1 ms\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eInput Scan Rate:\u003c\/strong\u003e 20 ms (Normal); 5 ms (Low Latency)\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eGalvanic Isolation:\u003c\/strong\u003e 1500 VAC RMS or ±1500 VDC\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eIsolation Technique:\u003c\/strong\u003e Optical (in IOM)\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003ePower Consumption:\u003c\/strong\u003e ~3.5 W (typical)\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eWeight:\u003c\/strong\u003e ~0.3 – 1.2 kg\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eKey Features\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eThree modes of operation: Normal (20 ms), SOE (1 ms + 20 ms PV), Low Latency (5 ms)\u003c\/li\u003e\n\u003cli\u003e1 ms SOE resolution for precise event timestamping\u003c\/li\u003e\n\u003cli\u003eOpen wire detection (Normal mode) for diagnostic integrity\u003c\/li\u003e\n\u003cli\u003eOptional redundancy for high-availability applications\u003c\/li\u003e\n\u003cli\u003eInternal or external field power selection\u003c\/li\u003e\n\u003cli\u003eOn-board excitation power (no marshalling required)\u003c\/li\u003e\n\u003cli\u003eSupplies non-incendive field power for hazardous areas\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eFAQ\u003c\/h3\u003e\n\u003cp\u003e\u003cstrong\u003eQ: What is the SOE resolution?\u003c\/strong\u003e\u003cbr\u003eA\u0026gt; The CC-PDIS01 provides \u003cstrong\u003e1 millisecond\u003c\/strong\u003e timestamp resolution for Sequence of Events applications.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: What IOTA bases are compatible?\u003c\/strong\u003e\u003cbr\u003eA\u0026gt; Compatible IOTAs include CC-TDIL01 (non-redundant, 9\"), CC-TCML11 (redundant, 12\"), CC-GDIL11 (redundant, 12\"), CC-GDIL21 (non-redundant, 6\").\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: Can I use this for standard digital input without SOE?\u003c\/strong\u003e\u003cbr\u003eA\u0026gt; Yes, the Normal mode (20 ms scan) operates as a standard 32-channel DI module without SOE timestamping.\u003c\/p\u003e\n\u003ch3\u003eInstallation Guidelines\u003c\/h3\u003e\n\u003col\u003e\n\u003cli\u003eMount the CC-PDIS01 on the appropriate IOTA base (CC-TDIL01, CC-TCML11, etc.).\u003c\/li\u003e\n\u003cli\u003eConfigure internal or external field power via jumper settings.\u003c\/li\u003e\n\u003cli\u003eConnect 24 VDC discrete field wiring to the terminal blocks.\u003c\/li\u003e\n\u003cli\u003eConfigure SOE mode via Experion PKS Control Builder if timestamping is required.\u003c\/li\u003e\n\u003cli\u003eVerify input status and SOE timestamps via Experion PKS diagnostics.\u003c\/li\u003e\n\u003c\/ol\u003e\n\u003ch3\u003eSelection Tips\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eChoose CC-PDIS01 when you need 1 ms SOE resolution for trip diagnostics or event sequencing.\u003c\/li\u003e\n\u003cli\u003eFor standard digital input without SOE, a standard DI module may be more cost-effective.\u003c\/li\u003e\n\u003cli\u003eVerify IOTA base model matches your redundancy and space requirements.\u003c\/li\u003e\n\u003c\/ul\u003e","brand":"Honeywell","offers":[{"title":"Default Title","offer_id":53862465929400,"sku":"CC-PDIS01","price":166.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0935\/6132\/3704\/files\/CC-PDIS01.png?v=1785909906","url":"https:\/\/www.globalpetroparts.com\/products\/honeywell-cc-pdis01-digital-input-sequence-of-events","provider":"Global Petro Parts Automation","version":"1.0","type":"link"}