{"product_id":"is200trtdh1d-general-electric-mark-vie-rtd-input-terminal-board","title":"IS200TRTDH1D | General Electric Mark VIe RTD Input Terminal Board","description":"\u003ch3\u003eGE IS200TRTDH1D Mark VI RTD Input Terminal Board — 16-Channel, 3-Wire, Simplex\u003c\/h3\u003e\n\u003cp\u003eThe \u003cstrong\u003eIS200TRTDH1D\u003c\/strong\u003e is an \u003cstrong\u003eRTD Input Terminal Board (TRTD)\u003c\/strong\u003e for GE's \u003cstrong\u003eMark VI\u003c\/strong\u003e turbine control platform. It accepts \u003cstrong\u003e16 three-wire RTD inputs\u003c\/strong\u003e via two barrier-type terminal blocks, with built-in \u003cstrong\u003enoise suppression and surge protection circuitry\u003c\/strong\u003e on each channel. The board connects to \u003cstrong\u003ePRTD I\/O packs\u003c\/strong\u003e via two DC-type 37-pin connectors, converting analog temperature signals into digital values for the controller. This is a \u003cstrong\u003esimplex-only\u003c\/strong\u003e board — TMR applications require TRTDH1B with VRTD boards.\u003c\/p\u003e\n\u003ch3\u003eKey Specifications\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eManufacturer:\u003c\/strong\u003e General Electric \/ GE Energy\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eSeries:\u003c\/strong\u003e Mark VI Speedtronic\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eType:\u003c\/strong\u003e RTD Input Terminal Board\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eChannels:\u003c\/strong\u003e 16 three-wire RTD inputs\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eTerminal Blocks:\u003c\/strong\u003e 2 barrier-type strips, 24 screw terminals each (48 total)\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eWire Gauge:\u003c\/strong\u003e Up to #12 AWG\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eConnectors:\u003c\/strong\u003e 2 female 37-pin DC-type connectors (JA1 and JB1) for PRTD I\/O pack connection\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eShield Terminals:\u003c\/strong\u003e Dedicated shield terminal strip connected to chassis ground per block\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eProtection:\u003c\/strong\u003e Noise suppression circuitry (high-frequency noise and surge protection) on all inputs\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eSoftware Features:\u003c\/strong\u003e System limit checking; hardware limit checking\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eHardware Configuration:\u003c\/strong\u003e No jumpers or configurable hardware\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eMounting:\u003c\/strong\u003e Two oval cutouts for screw mounting; notches along one edge and at two corners\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eCompatibility:\u003c\/strong\u003e PRTD I\/O pack; simplex applications only\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eStatus:\u003c\/strong\u003e Active \/ In production\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eArchitecture \u0026amp; Redundancy\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eSimplex Only:\u003c\/strong\u003e IS200TRTDH1D supports simplex PRTD I\/O pack connections only\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eTMR Variant:\u003c\/strong\u003e IS200TRTDH1B fans inputs to three VRTD boards in R, S, and T racks for TMR Mark VI systems\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eSignal Path:\u003c\/strong\u003e RTD inputs → TRTD terminal board → PRTD I\/O pack → digital temperature values → Mark VI controller\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eEnvironmental Compliance:\u003c\/strong\u003e Meets same environmental, resolution, suppression, and function requirements as TRTDH1C\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eInstallation Guide\u003c\/h3\u003e\n\u003col\u003e\n\u003cli\u003eMount the IS200TRTDH1D using the \u003cstrong\u003etwo oval cutouts\u003c\/strong\u003e for screw mounting.\u003c\/li\u003e\n\u003cli\u003eConnect \u003cstrong\u003e16 three-wire RTD sensor wires\u003c\/strong\u003e to the two barrier-type terminal blocks (24 terminals each).\u003c\/li\u003e\n\u003cli\u003eUse \u003cstrong\u003edouble-shielded wire\u003c\/strong\u003e for all RTD connections.\u003c\/li\u003e\n\u003cli\u003eTerminate all shields at the \u003cstrong\u003ededicated shield terminal strip\u003c\/strong\u003e on each block — end shields at the end device.\u003c\/li\u003e\n\u003cli\u003eConnect \u003cstrong\u003eJA1 and JB1 37-pin cables\u003c\/strong\u003e to the PRTD I\/O pack.\u003c\/li\u003e\n\u003cli\u003eVerify no jumpers are required — the board has \u003cstrong\u003eno configurable hardware\u003c\/strong\u003e.\u003c\/li\u003e\n\u003cli\u003ePower on and verify temperature readings via Mark VI CIMPLICITY HMI.\u003c\/li\u003e\n\u003c\/ol\u003e\n\u003ch3\u003eFAQ\u003c\/h3\u003e\n\u003cp\u003e\u003cstrong\u003eQ: Is IS200TRTDH1D for Mark VI or Mark VIe?\u003c\/strong\u003e\u003cbr\u003eA: \u003cstrong\u003eMark VI.\u003c\/strong\u003e The IS200 prefix indicates Mark VI series. Some sources incorrectly list it as Mark VIe — IS400 series is the Mark VIe RoHS equivalent.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: What is the difference between TRTDH1D and TRTDH1B?\u003c\/strong\u003e\u003cbr\u003eA: \u003cstrong\u003eTRTDH1D\u003c\/strong\u003e is a \u003cstrong\u003esimplex\u003c\/strong\u003e board with two DC connectors for PRTD. \u003cstrong\u003eTRTDH1B\u003c\/strong\u003e is a \u003cstrong\u003eTMR\u003c\/strong\u003e board that fans inputs to three VRTD boards in R, S, and T racks.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: What does the H1D suffix mean?\u003c\/strong\u003e\u003cbr\u003eA: \u003cstrong\u003e\"H1\"\u003c\/strong\u003e indicates the \u003cstrong\u003ehardware revision \/ functional variant\u003c\/strong\u003e. \u003cstrong\u003e\"D\"\u003c\/strong\u003e is the \u003cstrong\u003eD-rated functional revision\u003c\/strong\u003e identifying this as the simplex version.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: Does it support 2-wire or 4-wire RTDs?\u003c\/strong\u003e\u003cbr\u003eA: \u003cstrong\u003eThree-wire RTDs only.\u003c\/strong\u003e The terminal blocks are wired for 3-wire configuration. For 2-wire or 4-wire RTDs, use appropriate terminal boards or interposing devices.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: What RTD types are supported?\u003c\/strong\u003e\u003cbr\u003eA: Common RTD types (Pt100, Pt200, Cu10, etc.) are supported via PRTD I\/O pack configuration. Verify specific type compatibility with your PRTD firmware version.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: Can I use this board without a PRTD I\/O pack?\u003c\/strong\u003e\u003cbr\u003eA: \u003cstrong\u003eNo.\u003c\/strong\u003e The TRTDH1D requires a PRTD I\/O pack to convert analog RTD signals to digital temperature values for the controller.\u003c\/p\u003e\n\u003ch3\u003eSelection Tips\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eMark VI, 16 RTD inputs, simplex:\u003c\/strong\u003e IS200TRTDH1D + PRTD I\/O pack\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eMark VI, 16 RTD inputs, TMR:\u003c\/strong\u003e IS200TRTDH1B + 3× VRTD boards\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eMark VIe, RTD inputs:\u003c\/strong\u003e IS400TRTDH1D (RoHS equivalent)\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eAlways verify:\u003c\/strong\u003e Simplex vs. TMR requirement, RTD type (3-wire), and PRTD I\/O pack availability\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eUse double-shielded cable\u003c\/strong\u003e and proper shield termination for noise immunity\u003c\/li\u003e\n\u003c\/ul\u003e","brand":"GE Fanuc","offers":[{"title":"Default Title","offer_id":53730856239288,"sku":"IS200TRTDH1D","price":234.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0935\/6132\/3704\/files\/IS200TRTDH1C_3_1.jpg?v=1779673124","url":"https:\/\/www.globalpetroparts.com\/products\/is200trtdh1d-general-electric-mark-vie-rtd-input-terminal-board","provider":"Global Petro Parts Automation","version":"1.0","type":"link"}