{"product_id":"saed5d-yokogawa-terminal-board-digital-signal","title":"SAED5D | Yokogawa Terminal Board (Digital Signal)","description":"\u003ch3\u003eProduct Overview\u003c\/h3\u003e\n\u003cp\u003eThe \u003cstrong\u003eSAED5D\u003c\/strong\u003e is a digital signal terminal board for the Field I\/O (FIO) subsystem of Yokogawa CENTUM VP systems. It provides reliable field wiring connections for digital input\/output modules such as ADV151 and ADV551.\u003c\/p\u003e\n\n\u003ch3\u003eKey Features\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\u003cstrong\u003e32 points per set\u003c\/strong\u003e\u003c\/li\u003e\n\u003cli\u003eM4 screw terminals\u003c\/li\u003e\n\u003cli\u003eProtects connector pins and prevents dust accumulation\u003c\/li\u003e\n\u003cli\u003eHigh insulation resistance (≥100 MΩ at 500 V DC)\u003c\/li\u003e\n\u003cli\u003eSupports single and dual-redundant configurations\u003c\/li\u003e\n\u003c\/ul\u003e\n\n\u003ch3\u003eTechnical Specifications\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eNumber of Points\u003c\/strong\u003e: 32\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eTerminal Type\u003c\/strong\u003e: M4 screws\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eCompatible Modules\u003c\/strong\u003e: ADV151, ADV551, ADV161, ADV561\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eInsulation Resistance\u003c\/strong\u003e: ≥100 MΩ at 500 V DC\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eWithstanding Voltage\u003c\/strong\u003e: 500 V AC for 1 minute\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eWeight\u003c\/strong\u003e: Approximately 1.5 kg\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eSystem\u003c\/strong\u003e: CENTUM VP FIO subsystem\u003c\/li\u003e\n\u003c\/ul\u003e\n\n\u003ch3\u003eFAQ\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eWhat modules does it connect to?\u003c\/strong\u003e Digital I\/O modules such as ADV151 and ADV551.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eIs it suitable for redundant systems?\u003c\/strong\u003e Yes, two sets are required for dual-redundant configurations with ADV161\/ADV561.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eWhat cable is typically used?\u003c\/strong\u003e AKB337 or equivalent for 64-point setups.\u003c\/li\u003e\n\u003c\/ul\u003e\n\n\u003ch3\u003eInstallation Guide\u003c\/h3\u003e\n\u003col\u003e\n\u003cli\u003eMount the terminal board in the designated FIO location.\u003c\/li\u003e\n\u003cli\u003eConnect the signal cable (AKB331 or AKB337) to the digital I\/O module.\u003c\/li\u003e\n\u003cli\u003eTerminate field wiring on the M4 screw terminals according to the channel map.\u003c\/li\u003e\n\u003cli\u003eEnsure proper grounding and insulation.\u003c\/li\u003e\n\u003cli\u003eVerify continuity and system recognition after power-up.\u003c\/li\u003e\n\u003c\/ol\u003e\n\n\u003ch3\u003eSelection Tips\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eChoose SAED5D when a dedicated digital signal terminal board is required for CENTUM VP FIO.\u003c\/li\u003e\n\u003cli\u003eConfirm compatibility with the specific ADV-series module and cable length needs.\u003c\/li\u003e\n\u003cli\u003eOrder additional sets for redundant configurations.\u003c\/li\u003e\n\u003c\/ul\u003e","brand":"Yokogawa","offers":[{"title":"Default Title","offer_id":53978782924984,"sku":"SAED5D","price":176.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0935\/6132\/3704\/files\/SAED5D_3__._03780f0a-e581-49f8-af70-62e8f9893d1e.png?v=1787640953","url":"https:\/\/www.globalpetroparts.com\/products\/saed5d-yokogawa-terminal-board-digital-signal","provider":"Global Petro Parts Automation","version":"1.0","type":"link"}