{"product_id":"yokogawa-f3yd14-0n-transistor-output-module-14-point","title":"Yokogawa F3YD14-0N Transistor Output Module 14-point","description":"\u003ch3\u003eProduct Overview\u003c\/h3\u003e\n\u003cp\u003eThe \u003cstrong\u003eYokogawa F3YD14-0N\u003c\/strong\u003e is a \u003cstrong\u003e14-point sink-type transistor output module\u003c\/strong\u003e for the FA-M3 series, designed for reliable DC load switching in industrial automation systems. Delivering \u003cstrong\u003e2A per point\u003c\/strong\u003e and \u003cstrong\u003e14A per common\u003c\/strong\u003e at 12-24V DC, it provides robust direct drive capability for solenoid valves, relay coils, and indicator devices. With \u003cstrong\u003e1 ms switching response\u003c\/strong\u003e, \u003cstrong\u003eactive clamp surge protection\u003c\/strong\u003e, and \u003cstrong\u003ephotocoupler isolation\u003c\/strong\u003e, it ensures deterministic control and long service life in factory and process environments.\u003c\/p\u003e\n\n\u003ch3\u003eKey Specifications\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eOutput Type:\u003c\/strong\u003e Transistor contact (sink type, NPN)\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eNumber of Outputs:\u003c\/strong\u003e 14 points per common\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eRated Load Voltage:\u003c\/strong\u003e 12 to 24V DC\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eMaximum Load Current:\u003c\/strong\u003e 2A per point, 14A per common\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eResponse Time:\u003c\/strong\u003e OFF→ON: 1 ms max; ON→OFF: 1 ms max\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eON Voltage Drop:\u003c\/strong\u003e 0.5V DC max\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eOff-State Leakage Current:\u003c\/strong\u003e 0.1 mA max\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eSurge Protection:\u003c\/strong\u003e Active clamp surge protector\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eIsolation:\u003c\/strong\u003e Photocoupler isolation\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eCPU Error Output:\u003c\/strong\u003e HOLD\/RESET configurable for each of the 14 points\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eCurrent Consumption:\u003c\/strong\u003e 100 mA at 5V DC\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eExternal Power Supply:\u003c\/strong\u003e 12 to 24V DC, 10 mA\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eConnection:\u003c\/strong\u003e 14-point terminal block, M3.5 screws\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eOperating Temperature:\u003c\/strong\u003e -20 to 65°C\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eWeight:\u003c\/strong\u003e 300 g (0.3 kg)\u003c\/li\u003e\n\u003c\/ul\u003e\n\n\u003ch3\u003eCompatibility \u0026amp; Applications\u003c\/h3\u003e\n\u003cp\u003eCompatible with all FA-M3 base modules and CPU units. Perfect for \u003cstrong\u003esolenoid valve banks, DC relay driving, pneumatic cylinder control, status indicator panels, and general 24V DC load switching\u003c\/strong\u003e in manufacturing, packaging, material handling, and process control applications.\u003c\/p\u003e\n\n\u003ch3\u003eFAQ\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eQ: What is the difference between F3YD14-0N and F3YD14-5A?\u003c\/strong\u003e A: F3YD14-0N provides 2A per point (14 points), while the officially cataloged F3YD14-5A provides 0.5A per point. Select based on your load current requirements.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eQ: Can I drive inductive loads like solenoids directly?\u003c\/strong\u003e A: Yes, the built-in active clamp surge protector handles inductive kickback. For very large coils, external flyback diodes are still recommended.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eQ: Is hot-swapping supported?\u003c\/strong\u003e A: No. Always power off the FA-M3 base unit and external field power before inserting or removing the module to prevent driver stress and transient faults.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eQ: What wire gauge is recommended?\u003c\/strong\u003e A: Use 0.75-1.25 mm² (18-16 AWG) wire with the M3.5 terminal screws, ensuring proper torque for reliable contact.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eQ: Does each output have individual isolation?\u003c\/strong\u003e A: Outputs share a common reference structure with channel-to-channel isolation at the driver level. Full galvanic isolation per channel is not specified.\u003c\/li\u003e\n\u003c\/ul\u003e\n\n\u003ch3\u003eInstallation Guide\u003c\/h3\u003e\n\u003col\u003e\n\u003cli\u003ePower off the FA-M3 system and external 24V DC field power.\u003c\/li\u003e\n\u003cli\u003eInsert F3YD14-0N into any available I\/O slot on the base module.\u003c\/li\u003e\n\u003cli\u003eConnect DC loads to the 14-point terminal block, observing correct polarity for sink-type wiring.\u003c\/li\u003e\n\u003cli\u003eApply external 12-24V DC power to the module power input terminals.\u003c\/li\u003e\n\u003cli\u003eConfigure CPU error response (HOLD or RESET) for each output via WideField3.\u003c\/li\u003e\n\u003cli\u003eRestore power and systematically test all 14 outputs using ladder logic or monitor mode.\u003c\/li\u003e\n\u003cli\u003eVerify terminal torque and cable routing, keeping output wiring separated from analog and communication lines.\u003c\/li\u003e\n\u003c\/ol\u003e\n\n\u003ch3\u003eSelection Tips\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eSelect F3YD14-0N for \u003cstrong\u003e14-point high-current DC output\u003c\/strong\u003e applications requiring 2A per point.\u003c\/li\u003e\n\u003cli\u003eFor lower current (0.5A) at 14 points, the standard catalog model F3YD14-5A is available.\u003c\/li\u003e\n\u003cli\u003eFor 8-point applications at 1A, F3YD08-6A provides a more compact and cost-effective solution.\u003c\/li\u003e\n\u003cli\u003eFor 32-point density at 0.1A, F3YD32-1A maximizes I\/O density per slot.\u003c\/li\u003e\n\u003cli\u003eCalculate total external power supply requirements: module overhead (10 mA) + sum of all load currents.\u003c\/li\u003e\n\u003cli\u003eMaintain proper cabinet grounding and low-impedance earth reference to minimize switching noise coupling.\u003c\/li\u003e\n\u003c\/ul\u003e","brand":"Yokogawa","offers":[{"title":"Default Title","offer_id":53930313580728,"sku":"F3YD14-0N","price":123.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0935\/6132\/3704\/files\/F3YD14-0N_c710a0b9-45cd-44d5-b66e-f7faf1918c49.png?v=1786950506","url":"https:\/\/www.globalpetroparts.com\/products\/yokogawa-f3yd14-0n-transistor-output-module-14-point","provider":"Global Petro Parts Automation","version":"1.0","type":"link"}