{"product_id":"yokogawa-sai533-h33-prp-prosafe-rs-analog-output-module","title":"Yokogawa SAI533-H33\/PRP ProSafe-RS Analog Output Module","description":"\u003ch3\u003eProduct Overview\u003c\/h3\u003e\n\u003cp\u003eThe\u003cspan\u003e \u003c\/span\u003e\u003cstrong\u003eYokogawa SAI533-H33\/PRP\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003eserves as a high-integrity analog output interface within the ProSafe-RS Safety Instrumented System (SIS). This module drives final control elements—such as emergency shutdown valves (ESV) and variable speed drives—using 8 isolated 4 to 20 mA channels. Engineered for functional safety applications, it integrates bidirectional HART communication to facilitate remote device diagnostics without compromising loop integrity. We supply this unit in\u003cspan\u003e \u003c\/span\u003e\u003cstrong\u003e100% Brand New and Original\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003econdition to ensure your safety loops meet the most stringent SIL3 requirements.\u003c\/p\u003e\n\u003ch3\u003ePart Number Breakdown\u003c\/h3\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr class=\"firstRow\"\u003e\n\u003ctd\u003e\u003cstrong\u003eSuffix\/Option Code\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e\u003cstrong\u003eDefinition\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e\u003cstrong\u003eEngineering Specification\u003c\/strong\u003e\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cspan\u003e\u003cstrong\u003eSAI533\u003c\/strong\u003e\u003c\/span\u003e\u003c\/td\u003e\n\u003ctd\u003e\u003cspan\u003eBase Model\u003c\/span\u003e\u003c\/td\u003e\n\u003ctd\u003e\u003cspan\u003eAnalog Output Module (4-20 mA, 8-channel, module isolation)\u003c\/span\u003e\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cspan\u003e\u003cstrong\u003e-H\u003c\/strong\u003e\u003c\/span\u003e\u003c\/td\u003e\n\u003ctd\u003e\u003cspan\u003eCommunication\u003c\/span\u003e\u003c\/td\u003e\n\u003ctd\u003e\u003cspan\u003eSupports digital communication via HART protocol\u003c\/span\u003e\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cspan\u003e\u003cstrong\u003e3\u003c\/strong\u003e\u003c\/span\u003e\u003c\/td\u003e\n\u003ctd\u003e\u003cspan\u003eInterface\u003c\/span\u003e\u003c\/td\u003e\n\u003ctd\u003e\u003cspan\u003eSignal cable interface adapter (Standard type)\u003c\/span\u003e\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cspan\u003e\u003cstrong\u003e3\u003c\/strong\u003e\u003c\/span\u003e\u003c\/td\u003e\n\u003ctd\u003e\u003cspan\u003eProtection\u003c\/span\u003e\u003c\/td\u003e\n\u003ctd\u003e\u003cspan\u003eISA Standard G3 conformal coating \u0026amp; extended temp (-20 to 70ºC)\u003c\/span\u003e\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cspan\u003e\u003cstrong\u003e\/PRP\u003c\/strong\u003e\u003c\/span\u003e\u003c\/td\u003e\n\u003ctd\u003e\u003cspan\u003eOption\u003c\/span\u003e\u003c\/td\u003e\n\u003ctd\u003e\u003cspan\u003ePrevention pin of false insertion (Mechanical keying)\u003c\/span\u003e\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003ch3\u003eTechnical Specifications\u003c\/h3\u003e\n\u003cul class=\"list-paddingleft-2\"\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eOutput Channels:\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003e8 channels, module isolation.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eOutput Signal:\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003e4 to 20 mA DC.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eCommunication:\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003eHART protocol superimposed on analog signal.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eSafety Level:\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003eSuitable for SIL3 safety instrumented functions.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eOperating Temperature:\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003e-20 to 70 ºC (-4 to 158 ºF).\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eEnvironment:\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003eISA Standard G3 compliant for corrosive gas resistance.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eMechanical Protection:\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003eIntegrated prevention pins for correct slot alignment.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003ePower Consumption:\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003eMax 370 mA (24 V DC).\u003c\/p\u003e\n\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eEngineering Advantages\u003c\/h3\u003e\n\u003cul class=\"list-paddingleft-2\"\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eEliminate Installation Errors:\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003eThe\u003cspan\u003e \u003c\/span\u003e\u003cstrong\u003e\/PRP\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003eoption incorporates mechanical prevention pins. These pins physically block the module from entering the wrong slot in the I\/O nest. This feature prevents accidental hardware damage and ensures that safety-critical loops remain correctly mapped during rapid maintenance or system expansion.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eSurvive Corrosive Environments:\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003eThe ISA Standard G3 conformal coating protects internal circuitry from aggressive pollutants like\u003cspan\u003e \u003c\/span\u003e\u003cspan class=\"math-inline\"\u003e$H_2S$\u003c\/span\u003e\u003cspan\u003e \u003c\/span\u003eand\u003cspan\u003e \u003c\/span\u003e\u003cspan class=\"math-inline\"\u003e$SO_2$\u003c\/span\u003e. This specialized barrier solves the problem of \"silver corrosion\" on the PCB, extending hardware life in non-climate-controlled marshaling cabinets or facilities near chemical processing zones.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eStreamline Valve Diagnostics:\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003eIntegrated HART support allows the ProSafe-RS system to monitor valve positioner health and execute partial stroke tests (PST) remotely. Engineers access critical asset data through the safety rack, reducing the need for manual inspections in hazardous field areas.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eHandle Thermal Extremes:\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003eThe robust hardware design maintains 0.1% accuracy across an extended temperature window of -20 to 70 ºC. This resilience ensures stable output to final control elements even when environmental conditions fluctuate in remote field enclosures.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eFAQs\u003c\/h3\u003e\n\u003cul class=\"list-paddingleft-2\"\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eHow does the \/PRP option assist in safety compliance?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eThe prevention pin ensures that maintenance personnel cannot accidentally insert an analog output module into a slot intended for a different signal type. This mechanical safeguard minimizes human error, a critical factor in maintaining the Functional Safety Management (FSM) integrity of the plant.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eIs this module compatible with standard 4-wire positioners?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eYes. The SAI533-H33\/PRP drives both 2-wire and 4-wire (self-powered) devices. Ensure you configure the field wiring and I\/O nest settings to match the specific impedance requirements of your positioner.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eCan I use the SAI533 in a non-safety DCS application?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eWhile physically similar to some CENTUM VP modules, the SAI533 is specifically certified for ProSafe-RS safety nests. It utilizes safety-certified diagnostics that standard DCS controllers do not support.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eWhat is the guarantee of originality?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eWe supply the SAI533-H33\/PRP in\u003cspan\u003e \u003c\/span\u003e\u003cstrong\u003e100% Brand New\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003efactory packaging. Each unit includes the original Yokogawa serial number and factory seal, ensuring the module has never been previously installed or refurbished.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003c\/ul\u003e","brand":"Yokogawa","offers":[{"title":"Default Title","offer_id":53439030362296,"sku":"SAI533-H33\/PRP","price":99.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0935\/6132\/3704\/files\/SAI533-H33.png?v=1778058051","url":"https:\/\/www.globalpetroparts.com\/products\/yokogawa-sai533-h33-prp-prosafe-rs-analog-output-module","provider":"Global Petro Parts Automation","version":"1.0","type":"link"}