Product Summary
The Allen-Bradley 1756-DHRIOK is a ControlLogix DH+/RIO Communication Module Kit by Rockwell Automation. It provides 2 configurable channels supporting both Data Highway Plus (DH+) messaging and Remote I/O (RIO) scanner functionality. The -K suffix denotes a kit configuration that includes the module and terminal blocks for quick installation. It enables communication between ControlLogix controllers and legacy DH+ networks, PLC-5 processors, SLC 500 systems, and remote I/O adapters.
Core Specifications
- Model Number: 1756-DHRIOK
- Type: DH+/RIO Bridge/Scanner Communication Module Kit
- Channels: 2 (independently configurable for DH+ or RIO)
- Communication Protocols: Data Highway Plus (DH+), Remote I/O (RIO), CIP Messaging
- Baud Rates: 57.6 kbps, 115.2 kbps, 230.4 kbps
- Connections: Up to 32 Logix connections; 32 RIO rack numbers per channel
- Backplane Current: 850 mA at 5.1V; 1.7 mA at 24V
- Power Dissipation: 4.4 W typical
- Weight: 0.38 kg
- Manufacturer: Allen-Bradley by Rockwell Automation
Electrical & Functional Characteristics
- Channel Configuration: Each channel independently set via rotary switches for DH+ or RIO mode
- DH+ Node Address: 00–77 octal, set via front-panel switches
- RIO Scanner: Scans up to 32 rack numbers per channel in round-robin fashion
- Message Routing: Supports bridging between DH+ and other networks (ControlNet, EtherNet/IP)
- Block Transfer: Supports block-transfer read/write with remote I/O adapters
- Status Indicators: Module status, channel A/B activity, and diagnostic LEDs
- Cable: Belden 9463 twinaxial (standard); Belden 89463 (XT version)
System Integration & Compatibility
- Primary Platform: ControlLogix 1756 chassis
- Compatible Devices: PLC-5, SLC 500, 1794-ASB, 1771-ASB, 1747-ASB, PanelView terminals, 1336 drives
- Software: RSLogix 5000 / Studio 5000 Logix Designer
- Configuration: Rotary switches for network type and node address; software configuration for RIO adapter lists
- Hot Swap: Supports removal and insertion under power (RIUP)
- Keying: Electronic keying prevents incorrect module insertion
- Related Parts: 1756-DHRIO (module only), 1756-DHRIOXT (Xtreme temperature), 1756-RIO (RIO only module)
Environmental & Operational Limits
- Operating Temperature: 0°C to 60°C (32°F to 140°F)
- Storage Temperature: -40°C to +85°C (-40°F to 185°F)
- Humidity: 5% to 95% RH, non-condensing
- Vibration: 2 m/s², 10 to 500 Hz
- Shock: 30G operating; 50G non-operating
- Approvals: CE, CSA, KC (KCC), RCM, ATEX (Zone 2 with certified enclosure), Marine
Industrial Applications
Widely deployed in manufacturing modernization projects, legacy PLC-5 migrations, distributed I/O systems, SCADA networks, and process control applications requiring integration between ControlLogix platforms and existing DH+ or Remote I/O infrastructure.
Frequently Asked Questions
What is the 1756-DHRIOK used for?
It is a communication module kit that bridges ControlLogix controllers to legacy Data Highway Plus (DH+) networks and Remote I/O (RIO) devices, enabling migration and coexistence with older Allen-Bradley systems.
What does the -K suffix mean?
The -K indicates a kit configuration that includes the module and terminal blocks. The 1756-DHRIO is the module only.
Can both channels run different protocols simultaneously?
Yes — each channel is independently configurable. For example, Channel A can run DH+ while Channel B runs RIO scanner mode.
What cable do I need for the DH+/RIO network?
Use Belden 9463 twinaxial cable for standard installations. For Xtreme temperature applications, use Belden 89463.
What are the related part numbers?
- 1756-DHRIO — DH+/RIO module only
- 1756-DHRIOK — DH+/RIO module kit with terminal blocks (this part)
- 1756-DHRIOXT — Xtreme temperature version (-20°C to +70°C)
- 1756-RIO — Remote I/O only communication module
Return policy
We aim to provide reliable products and a smooth purchasing experience. If there is a problem with your order, please contact us and we will assist according to our Refund Policy.
Shipping
We provide international shipping options to meet different delivery requirements. Please review details regarding methods and timelines in our Shipping Policy.
Warranty
We provide a 12-month warranty for all products, subject to normal use and proper installation.
You may also like
Product Guide
Mitigating SCADA Performance Drops During Shift Transitions
Mitigating SCADA Performance Drops During Shift Transitions
Optimizing SCADA Performance: Why Remote Clients Experience Lag
Optimizing SCADA Performance: Why Remote Clients Experience Lag