ABB
DI880 | ABB 16 Channel SIL3 High Integrity Digital Input Module
Manufacturer: ABB
Product No.: DI880
Product Type: Digital Input
Product Origin: Switzerland
Payment:T/T, Western Union
Weight: 350g
Shipping port: Xiamen
Warranty: 12 months
Product Overview
The ABB DI880 (3BSE028586R1) is a 16-channel SIL3-certified High Integrity digital input module for the S800 I/O system. It provides 24 V DC current-sinking inputs with extended diagnostics, Sequence of Events (SOE) capability at 1 ms resolution, and individual sensor power supplies per channel, making it ideal for safety instrumented systems (SIS).
Key Specifications
- Manufacturer: ABB
- Part Number: DI880 (3BSE028586R1)
- Product Type: High Integrity Digital Input Module
- System: S800 I/O
- Channels: 16 (1 group of 16)
- Voltage: 24 V DC (18–30 V DC)
- Input Current: 7 mA at 24 V DC
- Type: Current sinking
- Safety Rating: SIL3 certified per IEC 61508
- SOE: Yes, 1 ms resolution, up to 512 × 16 events queue
- Diagnostics: Extended (open wire, short circuit, process voltage supervision)
- Sensor Power: One current-limited transducer power output per input
- Isolation: Optical isolation per channel
- Redundancy: Supported (single or redundant configuration)
- MTU Compatibility: TU810, TU812, TU814, TU818, TU830, TU833, TU842, TU843, TU852
- Dimensions: 45 × 119 × 102 mm (W×H×D)
- Weight: 0.15 kg
Applications
- Safety instrumented systems (SIL3)
- Emergency shutdown (ESD) logic
- Burner management systems
- Critical process interlocks
- Sequence of Events recording
FAQ
Q: What makes DI880 different from DI840?
A: DI880 is SIL3-certified for High Integrity safety applications, while DI840 offers extended diagnostics but is not SIL-rated. DI880 also includes SOE with 1 ms resolution.
Q: Can DI880 be used in redundant configurations?
A: Yes, DI880 supports both single and redundant configurations when mounted on compatible redundancy MTUs (TU842/TU843/TU852).
Q: What MTU should I use for SIL3 applications?
A: Use TU830, TU833, TU842, TU843, or TU852 to leverage the built-in current-limited sensor power supplies required for SIL compliance.
Installation Guide
- Mount DI880 on a compatible MTU (TU830/TU833 for single, TU842/TU843/TU852 for redundant).
- Wire 24 V DC digital inputs using the MTU screw terminals.
- Connect sensor power from the MTU's current-limited outputs to field devices.
- Enable SOE and configure filter times (0–127 ms) in Control Builder M.
- Verify SIL3 configuration per ABB Safety Manual requirements.
Selection Tips
- Order DI880 exclusively for safety-critical loops requiring SIL3 integrity.
- Pair with SIL-certified controllers (PM865/PM867 with SM811/SM812) for complete safety loops.
- Use shielded field cables with overall shield for proper EMC compliance.
- For non-safety digital inputs, DI810 or DI840 are more economical alternatives.
Return policy
We aim to provide reliable products and a smooth purchasing experience. If there is a problem with your order, please contact us and we will assist according to our Refund Policy.
Shipping
We provide international shipping options to meet different delivery requirements. Please review details regarding methods and timelines in our Shipping Policy.
Warranty
We provide a 12-month warranty for all products, subject to normal use and proper installation.
You may also like
Product Guide
Mitigating SCADA Performance Drops During Shift Transitions
Mitigating SCADA Performance Drops During Shift Transitions
Optimizing SCADA Performance: Why Remote Clients Experience Lag
Optimizing SCADA Performance: Why Remote Clients Experience Lag