GE Fanuc
GE Fanuc Analog Input Module IC694ALG223
Manufacturer: GE Fanuc
Product No.: IC694ALG223
Product Type: Analog Input Module
Product Origin: USA
Payment:T/T, Western Union
Weight: 110g
Shipping port: Xiamen
Warranty: 12 months
Product Overview
The GE IC694ALG223 is a 16-Channel Analog Current Input Module for the Emerson PACSystems RX3i programmable automation controller platform. It provides single-ended current inputs configurable for 4-20 mA, 0-20 mA, or 4-20 mA Enhanced ranges, with alarm limits and open-wire fault detection capabilities.
Key Specifications
- Model Number: IC694ALG223
- Series: PACSystems RX3i
- Product Type: Analog Current Input Module
- Channels: 16 single-ended inputs
-
Input Ranges (Software Configurable):
- 4 to 20 mA
- 0 to 20 mA
- 4 to 20 mA Enhanced (with open-wire fault detection)
- Input Filter Response: 200 Hz
- Maximum Input Circuit Current: 65 mA
- Power Consumption: 120 mA @ +5VDC (backplane); 65 mA @ +24VDC isolated (plus current loop current(s))
- Resolution: 12 binary bits (A/D converter)
- Absolute Accuracy: ±0.25% of full scale @ 25°C; ±0.5% @ 0-60°C
- Update Rate: 15 milliseconds (all 16 channels)
- Operating Temperature: 0°C to 60°C (32°F to 140°F)
- Storage Temperature: -40°C to 85°C
- Humidity: 5% to 95% (non-condensing)
LED Indicators
-
MODULE OK LED:
- ON: Status OK, module configured
- OFF: No backplane power or watchdog timeout
- Rapid flashing: Configuration data not received from CPU
- Slow flashes then OFF: Failed power-up diagnostics or code execution error
- User Supply LED: Indicates external 24 VDC supply is within specifications
Core Features
- 16-channel high-density current input
- Three configurable input ranges including Enhanced for open-wire detection
- High and low alarm limits on all ranges
- 4-20 mA Enhanced range detects open-wire faults (4 mA to 0 mA)
- Module status and external power status reporting to CPU
- Built-in protection allows 32 mA fast blow fuse per channel
Applications
- 4-20 mA process transmitter monitoring
- Multi-point current loop data acquisition
- Open-wire fault detection in critical loops
- Process variable trending and logging
FAQ
Q: What is the difference between 4-20 mA and 4-20 mA Enhanced?
A: The 4-20 mA Enhanced range allows setting a low alarm limit down to 0 mA, providing open-wire fault detection. Standard 4-20 mA range cannot detect open-wire conditions.
Q: How much external 24V power is required?
A: The module requires 65 mA from the user-supplied +24 VDC isolated supply, plus the current loop current(s) from all active channels.
Installation Guide
- Power down the RX3i rack before installation.
- Insert the IC694ALG223 into any I/O slot of the RX3i universal backplane.
- Connect 4-20 mA field signals to the input terminals.
- Provide external +24 VDC isolated power supply.
- Configure channels, ranges, and alarm limits via RX3i programming software.
- Verify MODULE OK and User Supply LEDs indicate proper operation.
Selection Tips
- For voltage input, use IC694ALG222 (16-channel voltage input).
- For universal input (TC/RTD/Voltage/Current), use IC695ALG600.
- For 8-channel current input, use IC694ALG221.
- Install 32 mA fast blow fuses externally for channel protection.
Return policy
We aim to provide reliable products and a smooth purchasing experience. If there is a problem with your order, please contact us and we will assist according to our Refund Policy.
Shipping
We provide international shipping options to meet different delivery requirements. Please review details regarding methods and timelines in our Shipping Policy.
Warranty
We provide a 12-month warranty for all products, subject to normal use and proper installation.
You may also like
Product Guide
Mitigating SCADA Performance Drops During Shift Transitions
Mitigating SCADA Performance Drops During Shift Transitions
Optimizing SCADA Performance: Why Remote Clients Experience Lag
Optimizing SCADA Performance: Why Remote Clients Experience Lag