Honeywell
Honeywell 2MLF-DV8A 8-Channel Analog Voltage Output Module
Manufacturer: Honeywell
Product No.: 2MLF-DV8A
Product Type: Analog Output Module
Product Origin: USA
Payment:T/T, Western Union
Weight: 1100g
Shipping port: Xiamen
Warranty: 12 months
Product Overview
The Honeywell 2MLF-DV8A is an 8-channel analog voltage output module for the MasterLogic-200 (ML200) PLC system. It provides 0–10V DC output signals to field actuators, servo drives, and VFDs, enabling precise control of motor speed, valve position, and process variables. With 12-bit resolution and photo-coupler isolation, it delivers reliable, noise-immune analog control for industrial automation and process control applications.
Key Specifications
- Product Type: 8-Channel Analog Voltage Output Module
- Series: MasterLogic-200 / ML200
- Output Channels: 8
- Output Type: Voltage (DC 0–10V)
- Resolution: 12-bit
- Accuracy: ±0.5% FS at 25°C
- Conversion Speed: 2 ms / 8 channels
- Load Resistance: ≥ 2 kΩ
- Isolation: Photo-coupler isolation between output and internal logic
- External Power Supply: DC 24V (20.4–28.8V)
- Current Consumption: 70 mA (from 5V internal bus)
- External Connection: 18-point removable terminal block
- Dimensions (W x H x D): 27.4 mm x 90 mm x 70 mm
- Weight: Approx. 110 g
- Operating Temperature: 0°C to +55°C
Features & Benefits
- 8-channel voltage output — high-density 0–10V control for servo drives, VFDs, and proportional valves in a single slot
- 12-bit resolution — 0.025V precision enables smooth motor speed control and accurate valve positioning
- Photo-coupler isolation — 560V AC isolation protects the CPU from ground loops and field-side surges
- Fast 2 ms conversion — 250 μs per channel update rate supports real-time servo and drive control
- High load impedance (≥2 kΩ) — compatible with standard VFD analog inputs and servo drive command inputs without signal loading
Typical Applications
- VFD speed reference control (0–10V) for pumps and fans
- Servo drive command voltage for positioning systems
- Proportional valve control in hydraulic systems
- Heater power controller voltage input
- Building automation damper and valve actuators
- Any application requiring 0–10V DC control signals
Installation Guide
- Verify actuator input type — confirm your drives and actuators accept 0–10V DC input.
- Install in I/O slot — mount the 2MLF-DV8A in any available ML200 I/O slot.
- Connect 24V external power — wire DC 24V to the external power terminals.
- Wire field devices — connect V+ and COM terminals to the actuator's analog input using shielded cable.
- Configure output range — in SoftMaster, verify 0–10V range is selected and set hold-last or preset values for CPU fault conditions.
- Verify output — force 0%, 50%, and 100% output and confirm with a precision multimeter.
FAQ
Q: What is the difference between 2MLF-DV8A and 2MLF-DC8A?
A: The 2MLF-DV8A outputs voltage (0–10V DC). The 2MLF-DC8A outputs current (4–20 mA). Choose DV8A for VFDs and servo drives; choose DC8A for valve positioners and standard process actuators.
Q: Can I use this for 0–5V or 1–5V output?
A: No. The 2MLF-DV8A is fixed at 0–10V output. For other voltage ranges, use the 2MLF-DV4A (4-channel with selectable ranges) or scale in software.
Q: What is the minimum load resistance?
A: 2 kΩ minimum. Loads below 2 kΩ will cause output voltage droop and inaccurate control. Most VFDs and servo drives have >10 kΩ input impedance, which is compatible.
Selection Tips
- Choose 2MLF-DV8A when your field devices require 0–10V DC control signals.
- For 4–20 mA current output, select 2MLF-DC8A instead.
- Verify your drive/actuator input impedance is ≥2 kΩ before ordering.
- For mixed voltage ranges, consider the 2MLF-DV4A (4-channel with selectable ranges).
Return policy
We aim to provide reliable products and a smooth purchasing experience. If there is a problem with your order, please contact us and we will assist according to our Refund Policy.
Shipping
We provide international shipping options to meet different delivery requirements. Please review details regarding methods and timelines in our Shipping Policy.
Warranty
We provide a 12-month warranty for all products, subject to normal use and proper installation.
You may also like
Product Guide
Mitigating SCADA Performance Drops During Shift Transitions
Mitigating SCADA Performance Drops During Shift Transitions
Optimizing SCADA Performance: Why Remote Clients Experience Lag
Optimizing SCADA Performance: Why Remote Clients Experience Lag