Honeywell
Honeywell 2MLF-RD4A 4-Channel RTD Input Module
Manufacturer: Honeywell
Product No.: 2MLF-RD4A
Product Type: RTD Input Module
Product Origin: USA
Payment:T/T, Western Union
Weight: 1100g
Shipping port: Xiamen
Warranty: 12 months
Product Overview
The Honeywell 2MLF-RD4A is a 4-channel RTD (Resistance Temperature Detector) input module for the MasterLogic-200 (ML200) PLC system. It directly interfaces with Pt100, Pt1000, Cu50, and Cu100 RTD sensors, providing high-accuracy temperature measurement for process control, HVAC, and machine monitoring applications. With 16-bit resolution and built-in lead-wire compensation, it eliminates the need for external signal conditioners, reducing panel complexity and installation cost.
Key Specifications
- Product Type: 4-Channel RTD Input Module
- Series: MasterLogic-200 / ML200
- Input Channels: 4
- Sensor Types: Pt100, Pt1000, Cu50, Cu100 (3-wire or 4-wire)
- Measurement Range: -200°C to +850°C (Pt100)
- Resolution: 16-bit (0.1°C typical)
- Accuracy: ±0.1% FS at 25°C
- Conversion Speed: 80 ms / 4 channels
- Isolation: Channel-to-channel and channel-to-logic isolation
- Lead-Wire Compensation: Automatic 3-wire and 4-wire compensation
- External Connection: 20-point removable terminal block
- Current Consumption: 50 mA (from 5V internal bus)
- External Power: DC 24V (20.4–28.8V)
- Dimensions (W x H x D): 27.4 mm x 90 mm x 70 mm
- Weight: Approx. 100 g
- Operating Temperature: 0°C to +55°C
Features & Benefits
- Direct RTD interface — eliminates external transmitters and signal conditioners, reducing panel component count by 60% per temperature loop
- Automatic lead-wire compensation — 3-wire and 4-wire RTD support automatically nullifies cable resistance errors, ensuring ±0.1% accuracy even with long sensor cables
- Wide -200°C to +850°C range — covers cryogenic, ambient, and high-temperature process applications with a single module type
- 16-bit resolution — 0.1°C measurement granularity enables precise temperature control for pharmaceutical and food-grade batch processes
- Channel isolation — prevents ground loop errors when multiple RTDs are installed on different grounded vessels or pipes
Typical Applications
- Reactor jacket temperature monitoring in chemical plants
- Boiler steam temperature measurement in power generation
- HVAC chilled water and hot water supply temperature
- Food & beverage pasteurization and CIP temperature verification
- Pharmaceutical autoclave and freeze-dryer temperature control
- Motor bearing and gearbox oil temperature monitoring
Installation Guide
- Verify RTD type — confirm your sensors are Pt100, Pt1000, Cu50, or Cu100 and wired as 3-wire or 4-wire configuration.
- Install in I/O slot — mount the 2MLF-RD4A in any available ML200 I/O slot.
- Connect 24V external power — wire DC 24V to the external power terminals for the excitation circuits.
-
Wire RTD sensors — connect sensor leads to the appropriate terminals:
- 3-wire: Connect one lead to AI+, one to AI-, and the compensation lead to the EXC terminal.
- 4-wire: Connect two leads to AI+ and AI- (current injection), and two leads to S+ and S- (sense).
- Configure sensor type in SoftMaster — select Pt100, Pt1000, Cu50, or Cu100 and the wiring method (3-wire or 4-wire) in the CPU I/O parameters.
- Verify temperature reading — compare the PLC reading against a calibrated handheld thermometer at a known temperature point (e.g., ice bath at 0°C).
FAQ
Q: What is the difference between 2MLF-RD4A and 2MLF-RD8A?
A: The 2MLF-RD4A provides 4 RTD channels. The 2MLF-RD8A provides 8 RTD channels in the same footprint. Choose RD8A for high-density temperature monitoring; choose RD4A when 4 channels are sufficient and lower cost is preferred.
Q: Can I use thermocouples with this module?
A: No. The 2MLF-RD4A is for RTD sensors only. For thermocouples (J, K, T, E, R, S, B types), use the 2MLF-TC4S (4-channel isolated thermocouple input) module.
Q: What is the maximum cable length from sensor to module?
A: With 3-wire or 4-wire compensation, cable runs up to 500 meters are possible using 1.0 mm² or larger copper cable, depending on environmental noise.
Q: Does this module provide sensor excitation?
A: Yes. The 2MLF-RD4A provides constant current excitation to the RTD. No external excitation source is required.
Selection Tips
- Choose 2MLF-RD4A for 4-channel RTD temperature measurement in standard process applications.
- If you need 8 channels in the same slot, upgrade to 2MLF-RD8A.
- For thermocouple applications (high temperature >850°C), select 2MLF-TC4S instead.
- Always use shielded, twisted-pair cable for RTD wiring to minimize electromagnetic interference.
- Verify your RTD wiring configuration (3-wire vs. 4-wire) before ordering cable — 4-wire provides the highest accuracy but requires more conductors.
Return policy
We aim to provide reliable products and a smooth purchasing experience. If there is a problem with your order, please contact us and we will assist according to our Refund Policy.
Shipping
We provide international shipping options to meet different delivery requirements. Please review details regarding methods and timelines in our Shipping Policy.
Warranty
We provide a 12-month warranty for all products, subject to normal use and proper installation.
You may also like
Product Guide
Mitigating SCADA Performance Drops During Shift Transitions
Mitigating SCADA Performance Drops During Shift Transitions
Optimizing SCADA Performance: Why Remote Clients Experience Lag
Optimizing SCADA Performance: Why Remote Clients Experience Lag