Skip to product information
Honeywell 2MLQ-TR4B 32-Point Transistor Digital Output Module

Honeywell

Honeywell 2MLQ-TR4B 32-Point Transistor Digital Output Module

5 left
  • Manufacturer: Honeywell

  • Product No.: 2MLQ-TR4B

  • Product Type: Digital Output Module

  • Product Origin: USA

  • Payment:T/T, Western Union

  • Weight: 1600g

  • Shipping port: Xiamen

  • Warranty: 12 months

Special offer ends!
00 :
00 :
00

Product Overview

The Honeywell 2MLQ-TR4B is a 32-point transistor digital output module designed for the MasterLogic-200 (ML200) PLC system. Featuring source-type transistor outputs with photo-coupler isolation, this high-density module delivers fast, reliable switching for relays, solenoids, indicators, and other low-power DC loads. With a ≤1 ms response time and compact footprint, the 2MLQ-TR4B is ideal for real-time industrial automation in space-constrained control cabinets.

Key Features

  • 32 high-density transistor output points (source type)
  • Fast switching: ≤1 ms On/Off response time
  • Rated load voltage: DC 12 V / 24 V
  • Photo-coupler isolation for enhanced signal integrity and noise immunity
  • Zener diode surge protection per IEC 61000-6-2
  • 40-pin connector for compact, organized field wiring
  • Individual LED status indicators for each output channel
  • Compact design — 170 × 98 × 19 mm, 0.26 kg

Technical Specifications

  • Model: 2MLQ-TR4B
  • Product Type: Digital Output Module (Transistor, Source Type)
  • Series: MasterLogic-200
  • Output Channels: 32 points
  • Output Type: Transistor (Source Type)
  • Rated Load Voltage: DC 12 V / 24 V
  • Load Voltage Range: DC 10.2 V – 26.4 V
  • Max Load Current: 0.1 A per point, 2 A per COM
  • Voltage Drop (On): ≤ 0.3 V
  • Off Leakage Current: ≤ 0.1 mA
  • Inrush Current: 4 A for ≤ 10 ms
  • Response Time: ≤ 1 ms (On ↔ Off)
  • Isolation Method: Photo-coupler isolation
  • Surge Absorber: Zener diode
  • Common Method: 32 points / 1 COM
  • Current Consumption: 130 mA (all points ON)
  • External Voltage: DC 12/24 V ±10%, ripple ≤ 4 Vp-p
  • Connection: 40-pin connector
  • Cable Size: 0.3 mm²
  • Dimensions (W × H × D): 170 × 98 × 19 mm
  • Weight: 0.26 kg
  • Operating Temperature: 0°C to +55°C
  • Storage Temperature: −25°C to +70°C
  • Humidity: 5% to 95% RH (non-condensing)
  • Certifications: CE

Typical Applications

  • Discrete control of relays, contactors, and solenoid valves
  • LED indicator and alarm horn driving
  • SSR (solid-state relay) control in heating systems
  • High-speed interlock and sequencing logic
  • Compact control cabinets requiring high-density I/O

FAQ

Q: What type of outputs does the 2MLQ-TR4B provide?
A: It provides 32 source-type transistor outputs for DC 12/24 V loads.

Q: What is the maximum current per point?
A: 0.1 A per point, with a maximum of 2 A per common (COM).

Q: What connector is required for field wiring?
A: A standard 40-pin connector is required. Pre-assembled cable assemblies with remote terminal blocks are recommended for simplified field termination.

Q: Does the module support hot-swapping?
A: No. Rack power must be fully isolated and switched off before inserting or removing any I/O module to prevent backplane damage.

Q: Is there surge protection?
A: Yes, each output features an integrated Zener diode surge absorber compliant with IEC 61000-6-2.

Installation Guide

  1. Power Off: De-energize the entire MasterLogic-200 rack before installing the 2MLQ-TR4B.
  2. Slot Insertion: Align the module with the guide rails and press firmly into the selected I/O slot until the retention clips lock.
  3. Connector Wiring: Attach the 40-pin connector to the module front. Use 0.3 mm² stranded wire for field connections. Group loads by common to respect the 2 A per COM limit.
  4. External Power: Supply DC 12/24 V to the module's external power terminals. Verify ripple is ≤ 4 Vp-p.
  5. Load Verification: Ensure each load does not exceed 0.1 A continuous. For inductive loads, add external flyback diodes.
  6. Status Check: Power on the rack and confirm LED indicators illuminate correctly when outputs are activated via the PLC program.

Selection Tips

  • Choose the 2MLQ-TR4B for high-density DC output applications requiring fast transistor switching.
  • If you need relay outputs for AC loads or higher current capacity, consider the 2MLQ-RY2A or 2MLQ-RY2B relay output modules.
  • For sink-type transistor outputs, verify availability of the complementary model in your region.
  • Respect the 2 A per COM limit — distribute high-current loads across multiple commons or modules.
  • Account for inrush current (4 A for 10 ms) when driving capacitive or lamp loads.
Return policy

​We aim to provide reliable products and a smooth purchasing experience. If there is a problem with your order, please contact us and we will assist according to our Refund Policy.

Shipping

We provide international shipping options to meet different delivery requirements. Please review details regarding methods and timelines in our Shipping Policy.

Warranty

We provide a 12-month warranty for all products, subject to normal use and proper installation.