Product Overview
The Schneider Electric BMXAMI0410 is a 4-channel isolated high-level analog input module for the Modicon X80 platform. It supports multiple voltage and current ranges with 16-bit resolution and 24-bit A/D conversion for precise process measurement.
- Analogue Input Number: 4 isolated channels
- Input Types: ±20 mA, 0...20 mA, 4...20 mA, ±10 V, ±5 V, 0...10 V, 0...5 V, 1...5 V
- Analogue Input Resolution: 16 bits
- A/D Conversion: 24 bits
- Input Impedance: 10 MΩ (voltage) / 250 Ω + protective resistor (current)
- Permitted Overload: ±30 V (voltage ranges) / ±90 mA (current ranges)
- Read Cycle Time: Fast 1 ms + 1 ms × channels used; Nominal 5 ms for 4 channels
- Isolation Voltage: 300 V DC between channels; 1400 V DC channels to ground/bus
- Common Mode Rejection: 90 dB
- Status LEDs: RUN (green), channel diagnostic (green), ERR (red), I/O (red)
- Net Weight: 0.143 kg
- Power Consumption: Typical 0.82 W at 24 V DC / 0.32 W at 3.3 V DC
- Operating Temperature: 0...60 °C
Key Features
- Channel-to-channel isolation
- High-speed acquisition suitable for continuous process control
- Internal recalibration
- Compatible with Modicon M340 and M580
FAQ
- What signal ranges are supported? Voltage (±10 V, ±5 V, 0-10 V, 0-5 V, 1-5 V) and current (±20 mA, 0-20 mA, 4-20 mA).
- Is isolation provided between channels? Yes, full channel-to-channel isolation.
- What is the resolution? 16-bit analogue input resolution with 24-bit conversion.
- How is the module connected? Via a 20-way removable terminal block.
Installation Guide
- Insert the module into an available X80 rack slot and lock with the captive screw.
- Attach the 20-way terminal block.
- Wire sensors according to the selected voltage or current range configuration.
- Configure input type and filtering in EcoStruxure Control Expert.
- Verify channel diagnostic LEDs after power-up.
Selection Tips
- Select BMXAMI0410 for high-level isolated analog inputs requiring fast update rates.
- Use when channel isolation is mandatory for signal integrity.
- For non-isolated or higher channel density, evaluate BMXAMI0800 series.
- Confirm terminal block type (screw or spring) matches project standards.
Return policy
We aim to provide reliable products and a smooth purchasing experience. If there is a problem with your order, please contact us and we will assist according to our Refund Policy.
Shipping
We provide international shipping options to meet different delivery requirements. Please review details regarding methods and timelines in our Shipping Policy.
Warranty
We provide a 12-month warranty for all products, subject to normal use and proper installation.
You may also like
Product Guide
Mitigating SCADA Performance Drops During Shift Transitions
Mitigating SCADA Performance Drops During Shift Transitions
Optimizing SCADA Performance: Why Remote Clients Experience Lag
Optimizing SCADA Performance: Why Remote Clients Experience Lag