Schneider
Schneider BMXART0414 4-Ch Isolated Low-Level Temperature Input
Manufacturer: Schneider
Product No.: BMXART0414
Product Type: Analog Input Module
Product Origin: USA
Payment:T/T, Western Union
Weight: 1800g
Shipping port: Xiamen
Warranty: 12 months
Product Overview
The Schneider Electric BMXART0414 is a 4-channel isolated low-level analog input module for Modicon X80, optimized for temperature measurement. It supports thermocouples, RTDs and low-level voltage signals with 15-bit + sign resolution.
- Analogue Input Number: 4 isolated channels
- Input Types: Thermocouple (B, E, J, K, L, N, R, S, T, U), RTD (Pt100, Pt1000, Ni100, Ni1000, Cu10 – 2/3/4-wire), Voltage (±40 mV to ±1.28 V)
- Analogue Input Resolution: 15 bits + sign
- A/D Conversion: Sigma-delta 16 bits
- Read Cycle Time: 200 ms (thermocouple) / 400 ms (RTD)
- Input Impedance: 10 MΩ
- Isolation Voltage: 750 V DC between channels / 1400 V DC channels to bus
- Common Mode Rejection: 120 dB at 50/60 Hz
- Status LEDs: RUN (green), channel diagnostic (green), ERR (red), I/O (red)
- Net Weight: 0.135 kg
- Current Consumption: 150 mA at 3.3 V DC / 40 mA at 24 V DC
- Operating Temperature: 0...60 °C
Key Features
- Full channel isolation for mixed sensor types
- Internal cold-junction compensation support
- First-order digital filtering
- Compatible with Modicon M340 and M580
FAQ
- Which sensors are supported? Thermocouples (B/E/J/K/L/N/R/S/T/U), RTDs (Pt/Ni/Cu 2/3/4-wire) and low-level voltage.
- What is the resolution? 15 bits + sign.
- Is channel isolation available? Yes, isolated between channels.
- How is connection made? Via a 40-way connector.
Installation Guide
- Install the module in an X80 rack slot.
- Connect the 40-way terminal block or cordset.
- Wire sensors according to 2-, 3- or 4-wire configuration and selected type.
- Configure sensor type, filtering and compensation in EcoStruxure Control Expert.
- Verify diagnostic LEDs and perform calibration checks if required.
Selection Tips
- Select BMXART0414 for multi-sensor temperature applications requiring isolation.
- Use when mixing thermocouple and RTD signals on the same module.
- For higher density, evaluate the 8-channel BMXART0814.
- Choose the H version for extended temperature or harsh environments.
Return policy
We aim to provide reliable products and a smooth purchasing experience. If there is a problem with your order, please contact us and we will assist according to our Refund Policy.
Shipping
We provide international shipping options to meet different delivery requirements. Please review details regarding methods and timelines in our Shipping Policy.
Warranty
We provide a 12-month warranty for all products, subject to normal use and proper installation.
You may also like
Product Guide
Mitigating SCADA Performance Drops During Shift Transitions
Mitigating SCADA Performance Drops During Shift Transitions
Optimizing SCADA Performance: Why Remote Clients Experience Lag
Optimizing SCADA Performance: Why Remote Clients Experience Lag