Triconex
Triconex 2352 32-Ch Analog Input 4-20mA TMR
Manufacturer: Triconex
Product No.: 2352
Product Type: Analog Input Module
Product Origin: USA
Payment:T/T, Western Union
Weight: 1600g
Shipping port: Xiamen
Warranty: 12 months
Product Overview
The 2352 is a 32-channel analog input module manufactured by Invensys Triconex for the Tricon safety instrumented system. It converts 4–20 mA DC current signals from field transmitters into digital values with 12-bit resolution and 0.15% full-scale accuracy. Designed with TMR architecture, each of the 32 commoned input channels is processed by three independent hardware paths, ensuring reliable data acquisition for safety-critical process variables such as pressure, temperature, flow, and level.
Key Specifications
- System: Invensys Triconex Tricon SIS
- Type: TMR Analog Input Module
- Channels: 32, commoned
- Nominal Input Current: 4–20 mA DC
- Operational Current Range: 2–22 mA DC
- Absolute Maximum Input Current: 50 mA DC
- Resolution: 12 bits
- Absolute Error: 0.15% of full scale (20 mA)
- Input Impedance (with Baseplate): 250 Ω
- Source Impedance: 180 Ω
- Input Bandwidth (3 dB): 16 Hz
- Scan Time: < 1 ms for all 32 points
- Functional-to-Protective-Earth Isolation: 500 VDC minimum
- Functional-to-Functional-Earth Isolation: 800 VDC minimum
Features & Benefits
- TMR Signal Integrity: Three independent input channels per point with mid-value selection eliminate erroneous readings from single-channel failures.
- High-Speed Scanning: Sub-millisecond scan time for all 32 points supports rapid safety logic execution for emergency shutdown systems.
- Precision Current Measurement: 0.15% accuracy and 12-bit resolution provide tight-tolerance control for critical process loops.
- Built-In Diagnostics: Force-to-value diagnostic (FVD) capability enables online verification of input channel health without process disruption.
- Overcurrent Protection: 50 mA absolute maximum input current protects internal circuitry from wiring faults and transmitter failures.
FAQ
Q: What is the difference between 2352 and 2351?
A: The 2352 is a 32-channel 4–20 mA analog input module. The 2351 is a 16-channel variant with similar signal conditioning. Both use TMR architecture.
Q: Does the 2352 provide loop power for 2-wire transmitters?
A> The module provides loop power for 2-wire 4–20 mA transmitters through the 250 Ω I-to-V resistor network. Verify total loop current against the module's power budget.
Q: Can the 2352 handle 0–20 mA signals?
A> The operational range is 2–22 mA, which covers both 4–20 mA and 0–20 mA signals. For 0–20 mA, the digital scaling is adjusted in TriStation 1131.
Installation Guide
- Install the module into a Tricon analog input slot in the chassis.
- Connect 2-wire or 4-wire transmitters to the external termination panel (ETP) terminals.
- Verify polarity on all current loop connections before energizing.
- Ground shielded cable drains at one end only (ETP ground bus) to prevent ground loops.
- Verify input accuracy by injecting a 4 mA, 12 mA, and 20 mA calibrated current source and comparing module readings.
Selection Tips
- Channel Count: The 2352 provides 32 channels. For 16-channel requirements, the 2351 offers a lower-density alternative.
- Signal Type: The 2352 is dedicated to 4–20 mA current inputs. For voltage inputs (0–5V, 0–10V), select the 3704E or 3700A.
- Isolation Needs: The 2352 is a commoned-input module. For channel-to-channel isolation, specify the 3703E isolated analog input module.
Return policy
We aim to provide reliable products and a smooth purchasing experience. If there is a problem with your order, please contact us and we will assist according to our Refund Policy.
Shipping
We provide international shipping options to meet different delivery requirements. Please review details regarding methods and timelines in our Shipping Policy.
Warranty
We provide a 12-month warranty for all products, subject to normal use and proper installation.
You may also like
Product Guide
Mitigating SCADA Performance Drops During Shift Transitions
Mitigating SCADA Performance Drops During Shift Transitions
Optimizing SCADA Performance: Why Remote Clients Experience Lag
Optimizing SCADA Performance: Why Remote Clients Experience Lag