Yokogawa
Yokogawa AAI543-S00 | 16-Channel 4-20mA Output Unit New
Manufacturer: Yokogawa
Product No.: AAI543-S00
Product Type: Output Unit
Product Origin: 日本
Payment:T/T, Western Union
Weight: 300g
Shipping port: Xiamen
Warranty: 12 months
Yokogawa AAI543-S00 16-Channel Isolated Analog Output Module
The AAI543-S00 (Model: AAI543) is a high-precision analog output module designed for Yokogawa’s CENTUM VP and CS 3000 distributed control systems (DCS). As a core component of the Field I/O (FIO) subsystem, the AAI543-S00 (Order Number: AAI543-S00) provides 16 isolated channels to drive field devices such as control valves, actuators, and signal converters. This module is engineered to convert digital control commands from the DCS into stable 4 to 20 mA DC current signals, ensuring deterministic process regulation.
A critical correction to common misinformation: the AAI543-S00 (Part Number: AAI543-S00) is an Analog Output Module, not an input module. It features galvanic isolation between the system and field circuits, as well as channel-to-channel isolation, which is essential for preventing ground loops and maintaining signal integrity in complex plant architectures. With its "Standard" (S) and "Basic" (00) suffix codes, it provides a reliable, cost-effective solution for mission-critical industrial applications in petrochemical, power generation, and water treatment sectors.
Detailed Technical Specifications
The AAI543-S00 (Model: AAI543-S00) delivers consistent performance through advanced digital-to-analog conversion and robust safety features.
| Feature | Details |
| Manufacturer | Yokogawa Electric Corporation |
| Model Number | AAI543-S00 |
| Product Type | Analog Output Module |
| Series | CENTUM VP / CS 3000 (FIO Subsystem) |
| Number of Channels | 16, isolated |
| Output Signal | 4 to 20 mA DC |
| Allowable Load Resistance | 0 to 750 Ω |
| Accuracy | ±48 µA (±0.3% of full scale) |
| Data Update Period | 10 ms |
| Withstanding Voltage | 1500 V AC between field and system |
| Redundancy | Supports dual-redundant configuration |
| Current Consumption | 230 mA (5 V DC), 290 mA (24 V DC) |
| External Connection | Pressure clamp terminal, MIL connector, or KS1 cable |
| Dimensions (W x H x D) | 32.8 × 107.5 × 130 mm |
| Weight | 0.3 kg (Net) / 1.5 kg (Shipping) |
| Operating Temperature | 0°C to +60°C |
Return policy
We aim to provide reliable products and a smooth purchasing experience. If there is a problem with your order, please contact us and we will assist according to our Refund Policy.
Shipping
We provide international shipping options to meet different delivery requirements. Please review details regarding methods and timelines in our Shipping Policy.
Warranty
We provide a 12-month warranty for all products, subject to normal use and proper installation.
You may also like
Product Guide
What is an Interposing Relay in a PLC System?
What is an Interposing Relay in a PLC System?
Rockwell CompactLogix 5380 Controller: Advancing Smart Manufacturing with Precision and Connectivity
Rockwell CompactLogix 5380 Controller: Advancing Smart Manufacturing with Precision and Connectivity