Product Overview
The Honeywell 05701-A-0302 is a Single Channel Control Card designed specifically for catalytic gas sensors within the Honeywell Zellweger Analytics System 57. It monitors combustible gas concentrations, providing clear and accurate readings with integrated sensor performance checks.
Key Specifications
- Model Number: 05701-A-0302
- Series: Honeywell System 57
- Product Type: Single Channel Control Card — Catalytic
- Operating Voltage: 18V to 32V DC
- Power Consumption: 3.75W (typical, including catalytic sensor)
- Electronic Drift: Less than ±2% over 6 months
-
Display: Multi-function display system
- Analogue: 25-segment for gas concentration
- Digital: Four-character numerical readout
- Message: Four-character for system messages
- Icon Section: Power and card selection indicators
- LED Indicators: A1, A2, A3 gas alarms; Fault and Inhibit
- Push-Buttons: Alarm reset, Card selection
- Dimensions: 170 mm × 25 mm × 112 mm (L × W × H)
- Weight: 0.165 kg
Core Features
- Self-contained single-channel catalytic gas detection processing
- 25-segment analog display plus 4-character digital readout
- Alarm setting resolution in 1% FSD steps
- Remote inhibit and alarm reset capability
- Self-validation of circuit components, software, and catalytic sensor condition
- Compatible with 05701-A-0284 Catalytic Sensor Drive Module
Applications
- Combustible gas detection (methane, propane, butane, etc.)
- LEL (Lower Explosive Limit) monitoring
- Refinery and petrochemical safety systems
- Offshore platform gas detection
- Wastewater treatment plant safety
FAQ
Q: What sensor drive module is required for the 05701-A-0302?
A: Use the 05701-A-0284 Catalytic Sensor Drive Module, which is factory-fitted and plugs directly onto the control card.
Q: What is the difference between 05701-A-0301 and 05701-A-0302?
A: The 05701-A-0301 is for 4-20 mA input sensors, while the 05701-A-0302 is specifically for catalytic (pellistor) type sensors.
Installation Guide
- Install the 05701-A-0284 Catalytic Sensor Drive Module onto the control card.
- Insert the assembled card into the System 57 sub-rack slot.
- Connect the catalytic sensor to the sensor drive module terminals.
- Configure alarm setpoints using the engineering card interface.
- Perform zero and span calibration with certified calibration gas.
- Verify sensor response and alarm functionality before commissioning.
Selection Tips
- Use 05701-A-0302 for catalytic (pellistor) combustible gas sensors.
- For 4-20 mA toxic gas sensors, use 05701-A-0301 instead.
- Consider the 05701-A-0285 Analogue Output Module for DCS integration.
- Ensure catalytic sensor compatibility with target gas type and measuring range.
Return policy
We aim to provide reliable products and a smooth purchasing experience. If there is a problem with your order, please contact us and we will assist according to our Refund Policy.
Shipping
We provide international shipping options to meet different delivery requirements. Please review details regarding methods and timelines in our Shipping Policy.
Warranty
We provide a 12-month warranty for all products, subject to normal use and proper installation.
You may also like
Product Guide
Mitigating SCADA Performance Drops During Shift Transitions
Mitigating SCADA Performance Drops During Shift Transitions
Optimizing SCADA Performance: Why Remote Clients Experience Lag
Optimizing SCADA Performance: Why Remote Clients Experience Lag