Honeywell
05701-A-0329 | Honeywell Triple DPCO (Double Pole Changeover) Relay Card
Manufacturer: Honeywell
Product No.: 05701-A-0329
Product Type: Relay Card
Product Origin: USA
Payment:T/T, Western Union
Weight: 300g
Shipping port: Xiamen
Warranty: 12 months
Product Overview
The Honeywell 05701-A-0329 is a Triple DPCO (Double Pole Changeover) Relay Card with integrated 4-20 mA analog output for the System 57 gas detection platform. It provides eight DPCO relays (two each for A1, A2, A3, plus Fault and Inhibit) and a proportional current loop output for external DCS/PLC integration.
Key Specifications
- Model Number: 05701-A-0329
- Series: Honeywell System 57
- Product Type: Triple DPCO Relay Card with 4-20mA Output
- Relay Configuration: 8 Total — 2× A1, 2× A2, 2× A3, 1× Fault, 1× Inhibit
- Relay Contact Type: Double Pole Change Over (DPCO)
- Analog Output: 4-20 mA Current Loop
- Output Accuracy: ±0.5% FS Typical
- Input Power: 24 VDC (via System 57 Backplane)
- Power Consumption: 1.6W
- Isolation: Galvanic isolation between channels and system logic
- Dimensions: 170 mm × 25 mm × 112 mm
- Weight: 245g (0.165 kg module; shipping weight 2.5 kg)
- Operating Temperature: -20°C to +50°C
Core Features
- Dual-functionality: relay outputs + 4-20 mA proportional signal retransmission
- Redundant DPCO switching logic with NO and NC contacts for fail-safe design
- Real-time concentration monitoring on SCADA via 4-20 mA output
- Galvanic isolation protects System 57 backplane from field-side noise
- Tiered alarm response: A1 (low-speed ventilation), A2 (high-speed exhaust), A3 (shutdown)
Applications
- Facility-wide gas safety and proportional process control
- SCADA/DCS integration for remote monitoring
- Emergency shutdown (ESD) systems
- Ventilation and damper control
- Fire and gas detection alarm management
FAQ
Q: How many relays does the 05701-A-0329 provide?
A: Eight relays total: two each for A1, A2, and A3 alarm levels, plus one Fault and one Inhibit relay.
Q: Is the 4-20 mA output compatible with third-party PLCs?
A: Yes, the standard 4-20 mA current loop ensures compatibility with Siemens, Rockwell, ABB, Yokogawa, and other industrial controllers.
Q: Does this card support hot-swapping?
A: No. Power down the System 57 rack before installation or removal to prevent backplane damage.
Installation Guide
- Power down the System 57 rack completely.
- Insert the relay card into the designated sub-rack slot.
- Connect field relay wiring to the DPCO terminals.
- Connect the 4-20 mA output to the external DCS/PLC input.
- Configure alarm setpoints and relay operation via the engineering card.
- Test all relay outputs and analog signal accuracy before commissioning.
Selection Tips
- Choose 05701-A-0329 when both relay outputs AND 4-20 mA retransmission are needed.
- For relay-only applications, consider 05701-A-0328 (Triple SPCO) or 05701-A-0327 (Double SPCO).
- For redundant relay outputs per alarm level, consider 05701-A-0330 (High Integrity).
- Verify load current requirements do not exceed 5A per relay contact.
Return policy
We aim to provide reliable products and a smooth purchasing experience. If there is a problem with your order, please contact us and we will assist according to our Refund Policy.
Shipping
We provide international shipping options to meet different delivery requirements. Please review details regarding methods and timelines in our Shipping Policy.
Warranty
We provide a 12-month warranty for all products, subject to normal use and proper installation.
You may also like
Product Guide
Mitigating SCADA Performance Drops During Shift Transitions
Mitigating SCADA Performance Drops During Shift Transitions
Optimizing SCADA Performance: Why Remote Clients Experience Lag
Optimizing SCADA Performance: Why Remote Clients Experience Lag