Schneider
140CRA93200 Schneider 140CRA93200 Remote I/O Adapter Modules
Manufacturer: Schneider
Product No.: 140CRA93200
Product Type: Remote I/O Adapter Modules
Product Origin: France
Payment:T/T, Western Union
Weight: 500g
Shipping port: Xiamen
Warranty: 12 months
Product Description
The 140CRA93200 is a Remote I/O (RIO) drop adapter for the Modicon Quantum automation platform. It enables distributed I/O expansion by connecting a remote Quantum rack to a central PLC processor over a coaxial S908 Remote I/O network. Designed for deterministic, high-reliability communication, the module ensures synchronized I/O updates across geographically distributed industrial systems.
Core Function
The 140CRA93200 interfaces the remote Quantum backplane with an S908 RIO head module, managing time-critical data exchange with minimal latency. It maintains deterministic I/O behavior required for high-availability and continuous-process applications.
Technical Specifications
| Parameter | Specification |
|---|---|
| Series | Modicon Quantum |
| Model | 140CRA93200 |
| Function | Remote I/O (RIO) Drop Adapter |
| Communication Protocol | S908 Remote I/O |
| Transmission Rate | 1.544 Mbit/s |
| Media Interface | Dual coaxial F-connectors (redundant) |
| Backplane Support | Full Quantum I/O rack (per head processor limits) |
| Backplane Current | 750 mA @ 5 VDC (typical) |
| Addressing | Rear rotary switches (Drop address 1–31) |
| Maximum Cable Length | Up to 15,000 ft (4,500 m) with repeaters |
| Diagnostics | LED indicators: Ready, Run, Modbus Plus, Comm Error |
| Maintenance Feature | Front sliding door with label area |
Installation & Maintenance
The 140CRA93200 supports hot swap in most Quantum configurations, allowing replacement without powering down the entire system (application permitting temporary RIO drop loss). The front-panel protective door safeguards internal components while allowing clear field labeling.
Application
Commonly used in distributed automation architectures, including:
-
Large process plants
-
Power generation and substations
-
Water and wastewater treatment
-
Material handling systems with remote I/O islands
FAQ
Does this module support Modbus Plus communication?
Yes. The module includes an integrated Modbus Plus (RS-485) port for programming terminals or HMI connections at the remote drop.
Can the 140CRA93200 be used as a standalone PLC interface?
No. This is a RIO drop module and must be paired with a RIO head module (e.g., 140CRP93100 or 140CRP93200) located at the CPU rack.
Return policy
We aim to provide reliable products and a smooth purchasing experience. If there is a problem with your order, please contact us and we will assist according to our Refund Policy.
Shipping
We provide international shipping options to meet different delivery requirements. Please review details regarding methods and timelines in our Shipping Policy.
Warranty
We provide a 12-month warranty for all products, subject to normal use and proper installation.
You may also like
Product Guide
What is an Interposing Relay in a PLC System?
What is an Interposing Relay in a PLC System?
Rockwell CompactLogix 5380 Controller: Advancing Smart Manufacturing with Precision and Connectivity
Rockwell CompactLogix 5380 Controller: Advancing Smart Manufacturing with Precision and Connectivity