ABB
3BSE051306R1 | ABB AI835A Analog Input Module - TC/MV
Manufacturer: ABB
Product No.: AI835A
Product Type: Analog Input
Product Origin: Switzerland
Payment:T/T, Western Union
Weight: 200g
Shipping port: Xiamen
Warranty: 12 months
Overview
The ABB AI835 3BSE051306R1 is an 8-channel differential analog input module designed for S800 I/O systems to process precision thermocouple and millivolt temperature signals from field instruments to process controllers.
Technical Specifications
- Product Type: Analog Input Module
- Part Number: 3BSE051306R1
- Model: AI835A
- Mechanics: S800
- Number of Channels: 8
- Signal Type: Differential inputs
- Linear Measurement Range: -30 to +75 mV
- Thermocouple Types: B, C, D, E, J, K, L, N, R, S, T, U
- Resolution: 15 bits
- Input Impedance: > 1 MΩ
- Isolation: Groupwise isolated from ground
- Maximum Error: 0.1%
- Temperature Drift: Typ. 5 ppm/°C, Max. 7 ppm/°C
- Update Cycle Time (50 Hz): 280 + 80 * (number of active channels) ms
- Update Cycle Time (60 Hz): 250 + 70 * (number of active channels) ms
- Maximum Field Cable Length: 600 meters
- CMRR (50Hz, 60Hz): 120 dB
- NMRR (50Hz, 60Hz): > 60 dB
- Rated Insulation Voltage: 50 V
- Dielectric Test Voltage: 500 V a.c.
- Power Dissipation: 1.6 W
- Current Consumption (+5 V Modulebus): 75 mA
- Current Consumption (+24 V Modulebus): 50 mA
- Current Consumption (+24 V External): 0 mA
- HART Communication: No
- SOE: No
- Redundancy: No
- High Integrity: No
- Intrinsic Safety: No
- Front LEDs: F(ault), R(un), W(arning)
- Supervision Diagnostics: Reference channels, power supply low, open-circuit wire break
- Cold Junction Channel 8 Range: -40 to 100 °C
- Compatible Module Termination Units (MTUs): TU810, TU812, TU814, TU818, TU830, TU833
- Width: 45 mm
- Depth: 102 mm (111 mm including connector)
- Height: 119 mm
- Weight: 0.22 kg
Key Features
- Provides 8 differential channels configurable for exact linear millivolt or high-density thermocouple tracking.
- Designates Channel 8 as a dedicated Cold Junction (CJ) reference compensation channel via 4-wire Pt100 RTD.
- Delivers advanced 15-bit analog-to-digital signal conversion with extremely low 7 ppm/°C maximum thermal drift.
- Features integrated continuous hardware supervision to detect and report wire-break open-circuit errors per channel.
- Maintains strong system integrity through groupwise galvanic isolation rated to withstand 500 V a.c. conditions.
Installation Notes
- Mount the module firmly onto a compatible S800 Module Termination Unit (MTU) including TU810 or TU833 inside a shielded enclosure.
- Connect thermocouple element wiring directly to the assigned MTU terminals ensuring proper cold junction reference settings.
- Ensure full functional earth connection of the DIN rail system to meet the designated 50 V rated insulation voltage specifications.
- Monitor the module front-panel F, R, and W status LEDs closely during initialization to verify error-free parameter loading.
Return policy
We aim to provide reliable products and a smooth purchasing experience. If there is a problem with your order, please contact us and we will assist according to our Refund Policy.
Shipping
We provide international shipping options to meet different delivery requirements. Please review details regarding methods and timelines in our Shipping Policy.
Warranty
We provide a 12-month warranty for all products, subject to normal use and proper installation.
You may also like
Product Guide
Mitigating SCADA Performance Drops During Shift Transitions
Mitigating SCADA Performance Drops During Shift Transitions
Optimizing SCADA Performance: Why Remote Clients Experience Lag
Optimizing SCADA Performance: Why Remote Clients Experience Lag