Skip to product information
6ES7134-6GD00-0BA1 Siemens SIMATIC ET 200SP AI 4xRTD/TC Analog Input Module

Siemens

6ES7134-6GD00-0BA1 Siemens SIMATIC ET 200SP AI 4xRTD/TC Analog Input Module

10 left
  • Manufacturer: Siemens

  • Product No.: 6ES7134-6GD00-0BA1

  • Product Type: Analog Input

  • Product Origin: Germany

  • Payment:T/T, Western Union

  • Weight: 260g

  • Shipping port: Xiamen

  • Warranty: 12 months

Special offer ends!
00 :
00 :
00

Product Overview

The Siemens 6ES7134-6GD00-0BA1 is an analog input module for the SIMATIC ET 200SP distributed I/O system. It provides 4 analog input channels for RTD (Resistance Temperature Detector) and thermocouple (TC) sensors, delivering precise temperature measurement for process control applications. With 16-bit resolution and wire-break monitoring, it ensures accurate, reliable temperature feedback in a compact 15 mm form factor.

Key Specifications

  • Module Type: Analog Input (AI)
  • Number of Inputs: 4 channels
  • Sensor Types: RTD (Pt100, Pt200, Pt500, Pt1000, Ni100, Ni1000, Cu10, etc.) and Thermocouple (Type J, K, N, R, S, T, E, B, C, U, L)
  • Resolution: 16 bits
  • Conversion Time: 50 ms per channel (configurable)
  • Measurement Ranges: -200°C to +850°C (RTD); -270°C to +1820°C (TC, type-dependent)
  • Wire-Break Monitoring: Yes, configurable per channel
  • Isolation: Galvanic isolation between channels and backplane
  • Base Unit Type: A0 or A1
  • Power Loss: Typ. 0.65 W
  • Dimensions (W × H × D): 15 mm × 73 mm × 58 mm

Compatibility & Applications

Compatible with ET 200SP interface modules (IM155-6 PN/DP) and BaseUnits type A0/A1. Perfect for reactor temperature monitoring, heat treatment furnace control, HVAC zone temperature sensing, food processing pasteurization, and pharmaceutical sterilization where multi-channel RTD/TC measurement is required.

FAQ

  • Q: Can each channel be configured for different sensor types? A: Yes, each of the 4 channels is independently configurable for RTD or TC types via TIA Portal.
  • Q: Does it support internal compensation for thermocouples? A: Yes, internal reference junction compensation is available. External compensation via Pt100 is also supported for higher accuracy.
  • Q: What base unit is required? A: BU type A0 (6ES7193-6BP00-0BA0) or A1 (6ES7193-6BP00-0BA1) is required. Verify your I/O module specifies A0/A1 compatibility.
  • Q: Is this module suitable for SIL-rated safety applications? A: This is a standard analog input module. For safety-rated temperature monitoring, use ET 200SP fail-safe AI modules.

Installation Guide

  1. Mount a compatible BaseUnit (BU15-P16+A0+2B or A1 variant) on the ET 200SP DIN rail.
  2. Insert 6ES7134-6GD00-0BA1 into the BaseUnit until fully seated.
  3. Connect RTD or thermocouple sensors to the push-in terminals, observing 3-wire or 4-wire RTD configurations.
  4. Configure sensor types, ranges, and wire-break monitoring in TIA Portal.
  5. Verify temperature readings match expected values using known reference points.

Selection Tips

  • Use 6ES7134-6GD00-0BA1 for 4-channel RTD/TC temperature measurement in ET 200SP systems.
  • For 8-channel density, consider 6ES7134-6JF00-0CA1 (8 AI, High Feature).
  • For voltage/current analog inputs, use 6ES7134-6GD00-0BA1 only if RTD/TC is required; otherwise select U/I-specific modules.
  • Use shielded extension cables for thermocouples to minimize EMI and ensure measurement accuracy.
Return policy

​We aim to provide reliable products and a smooth purchasing experience. If there is a problem with your order, please contact us and we will assist according to our Refund Policy.

Shipping

We provide international shipping options to meet different delivery requirements. Please review details regarding methods and timelines in our Shipping Policy.

Warranty

We provide a 12-month warranty for all products, subject to normal use and proper installation.