ABB AX561 – 4AI/2AO Analog I/O Module
The ABB AX561 (Product ID 1TNE968902R1301) is an analog input/output module for the AC500 S500 distributed I/O system. It features 4 analog input channels and 2 analog output channels with 12-bit resolution.
- Analog Inputs: 4 channels
- AI Ranges: 0–20 mA, 4–20 mA, 0–5 V, 0–10 V, −2.5 to +2.5 V, −5 to +5 V
- AI Resolution: 11-bit + sign
- Analog Outputs: 2 channels
- AO Ranges: 0–20 mA, 4–20 mA, −10 to +10 V
- AO Resolution: 12-bit + sign
- Conversion Time: 500 µs per channel
- Overvoltage Protection: 30 VDC
- Power Supply: 24 VDC
- Current Consumption: 0.14 A
- Surge Protection: 35 VDC for 0.5 s
- Max Power Dissipation: 4.9 W
- Protection: IP20
- Operating Temperature: 0°C to +60°C
- Storage Temperature: −40°C to +70°C
- Weight: 0.13 kg
- Dimensions: 74 mm × 135 mm × 34 mm
Technical Specifications
| Parameter | Value |
|---|---|
| Part Number | AX561 (1TNE968902R1301) |
| Product Type | Analog I/O Module |
| Analog Inputs | 4 |
| AI Ranges | 0–20 mA, 4–20 mA, 0–5 V, 0–10 V, ±2.5 V, ±5 V |
| AI Resolution | 11-bit + sign |
| Analog Outputs | 2 |
| AO Ranges | 0–20 mA, 4–20 mA, ±10 V |
| AO Resolution | 12-bit + sign |
| Conversion Time | 500 µs per channel |
| Power Supply | 24 VDC |
| Max Power | 4.9 W |
| Protection | IP20 |
| Temp Range | 0°C to +60°C |
| Weight | 0.13 kg |
| Dimensions | 74 × 135 × 34 mm |
FAQ
-
Signal Type Selection
Analog input channels support current and voltage signals. Each channel is individually configurable via AC500 Control Builder software. -
Bipolar Output
The two analog output channels support bipolar ±10 VDC signals. This is required for servo valve and motor drive control applications. -
Resolution
Analog inputs provide 11-bit plus sign resolution. Analog outputs provide 12-bit plus sign resolution. This delivers 0.05% measurement accuracy. -
Sensor Wiring
Analog inputs support 2-wire connection. Analog outputs use 1-wire connection. Shielded twisted pair cable is required for noise immunity.
Installation Guide
- Step 1: Mount the AX561 on the S500 terminal base. Ensure the DIN rail is properly grounded.
- Step 2: Connect 24 VDC supply to the module power terminals.
- Step 3: Wire analog signals using shielded twisted pair cable. Ground the shield at the module end only.
- Step 4: In AC500 Control Builder, select signal type per channel (mA or V), enable open-circuit detection, and set scaling.
- Step 5: Calibrate using precision signal source. Verify 4 mA reads 0% and 20 mA reads 100% of engineering range.
Selection Tips
Select AX561 for 4-channel analog input and 2-channel analog output in a single S500 module. It eliminates the need for separate AI and AO modules in small systems. For higher channel density, use dedicated AI5xx and AO5xx modules. Verify signal range requirements match the module specifications.
Return policy
We aim to provide reliable products and a smooth purchasing experience. If there is a problem with your order, please contact us and we will assist according to our Refund Policy.
Shipping
We provide international shipping options to meet different delivery requirements. Please review details regarding methods and timelines in our Shipping Policy.
Warranty
We provide a 12-month warranty for all products, subject to normal use and proper installation.
You may also like
Product Guide
Mitigating SCADA Performance Drops During Shift Transitions
Mitigating SCADA Performance Drops During Shift Transitions
Optimizing SCADA Performance: Why Remote Clients Experience Lag
Optimizing SCADA Performance: Why Remote Clients Experience Lag