Skip to product information
AI815 3BSE052604R1 Analog Input Module - HART | ABB S800 I/O

ABB

AI815 3BSE052604R1 Analog Input Module - HART | ABB S800 I/O

10 left
  • Manufacturer: ABB

  • Product No.: AI815

  • Product Type: Analog Input

  • Product Origin: Switzerland

  • Payment:T/T, Western Union

  • Weight: 200g

  • Shipping port: Xiamen

  • Warranty: 12 months

Special offer ends!
00 :
00 :
00

Overview

The ABB AI815 3BSE052604R1 is an 8-channel unipolar single-ended analog input module with HART communication capability designed for S800 I/O systems to process standard current and voltage signals from field transmitters while distributing current-limited power.

Technical Specifications

  • Product Type: Analog Input Module
  • Part Number: 3BSE052604R1
  • Model: AI815
  • Mechanics: S800
  • Number of Channels: 8
  • Signal Type: Unipolar single ended
  • Signal Specification: 0 to 20 mA, 4 to 20 mA, 0 to 5 V, 1 to 5 V
  • Resolution: 12 bit
  • HART Communication: Yes
  • SOE: No
  • Redundancy: No
  • High Integrity: No
  • Intrinsic Safety: No
  • Temperature Drift: Max. 50 ppm/°C
  • Input Filter (Rise Time 0-90%): 290 ms
  • Update Cycle Time: 10 ms
  • Current Limiting: Built-in current limited transmitter power
  • Maximum Field Cable Length: 600 meters
  • NMRR (50Hz, 60Hz): > 40 dB
  • Rated Insulation Voltage: 50 V
  • Dielectric Test Voltage: 500 V a.c.
  • Power Dissipation: 3.5 W
  • Current Consumption (+5 V Modulebus): 100 mA
  • Current Consumption (+24 V Modulebus): 50 mA
  • Keying Code: CC
  • Width: 45 mm
  • Depth: 102 mm (111 mm including connector)
  • Height: 119 mm
  • Weight: 0.23 kg

Key Features

  • Supports 8 channels for configurable voltage or current unipolar single-ended inputs.
  • Features integrated HART pass-through communication capability for smart field device diagnostics.
  • Provides built-in current limiting for transmitter power distribution to protect connected instruments.
  • Delivers stable 12-bit analog-to-digital resolution for accurate process measurement.
  • Utilizes groupwise isolation from ground to prevent common mode electrical noise interference.

Installation Notes

  • Mount the module onto a compatible S800 Module Termination Unit (MTU) inside a protected control cabinet.
  • Connect field transmitter wiring to the allocated MTU terminal blocks ensuring strict adherence to current or voltage circuit guidelines.
  • Ground the DIN rail and MTU framework properly to meet the 500 V a.c. dielectric isolation test requirement.
  • Verify communication link status and module configuration parameters via the control system software prior to final commissioning.
Return policy

​We aim to provide reliable products and a smooth purchasing experience. If there is a problem with your order, please contact us and we will assist according to our Refund Policy.

Shipping

We provide international shipping options to meet different delivery requirements. Please review details regarding methods and timelines in our Shipping Policy.

Warranty

We provide a 12-month warranty for all products, subject to normal use and proper installation.

You may also like