GE Fanuc
DS200DSPCH1A GE LS2100 Digital Signal Processor Control Board
Manufacturer: GE Fanuc
Product No.: DS200DSPCH1A
Product Type: LS2100 Digital Signal Processor Control Board
Product Origin: USA
Payment:T/T, Western Union
Weight: 620g
Shipping port: Xiamen
Warranty: 12 months
Product Overview
The GE DS200DSPCH1A (DS200DSPCH1A) serves as the computational core for the LS2100 Static Starter Control system. This Digital Signal Processor (DSP) board executes the high-speed mathematical algorithms required to control large synchronous motor starters during gas turbine ignition sequences. We supply this module as 100% Brand New original equipment. The DS200DSPCH1A functions by processing real-time feedback from the power conversion bridges and calculating precise firing angles for the silicon-controlled rectifiers (SCRs). Its primary role involves maintaining stable motor torque and acceleration profiles, ensuring the turbine reaches self-sustaining speeds without mechanical stress or electrical instability.
Technical Specifications
The DS200DSPCH1A utilizes a high-density architecture featuring dedicated signal processors and programmable logic devices.
| Feature | Specification |
| Model Number | DS200DSPCH1A |
| Manufacturer | General Electric (GE) |
| System Series | LS2100 Static Starter |
| Processor Type | High-speed Digital Signal Processor (DSP) |
| Interface Ports | RS-232, High-speed parallel backplane |
| Programming | Field-programmable via socketed EPROMs/Flash |
| Diagnostic Display | Multi-segment LED status indicators |
| Operating Temp | 0 to 55 Celsius |
| Cooling Requirement | Forced air within the LS2100 cabinet |
Engineering Advantages
The DS200DSPCH1A provides critical technical benefits for heavy-duty starting applications:
-
Deterministic Computational Performance: The board utilizes a dedicated DSP chip to calculate complex vector control equations in real-time. This eliminates processing jitter, ensuring perfectly synchronized gate firing even during the volatile current fluctuations typical of motor starting cycles.
-
Integrated Fault Diagnostics: GE engineers equipped the DSPCH1A with an array of onboard LEDs and diagnostic test points. These indicators provide instant visual feedback on processor health, communication link status, and internal power rail integrity, allowing technicians to isolate hardware issues in minutes.
-
High-Bandwidth Communication: The board features a high-speed parallel interface that facilitates near-instantaneous data exchange with the I/O and feedback modules. This ensures the control loop responds to overcurrent or overvoltage conditions within microseconds, protecting the expensive power bridge components.
-
Ruggedized Signal Integrity: Multi-layer PCB design and localized decoupling capacitors neutralize electromagnetic interference (EMI) generated by the high-power switching environment of the static starter. This preserves the accuracy of low-voltage control signals, preventing data corruption and nuisance trips.
FAQs
-
Does the DS200DSPCH1A require specific firmware upon installation?
Yes. The DS200DSPCH1A relies on firmware stored in socketed chips. If you are replacing an existing board, you must transfer the original EPROMs to the new unit or verify that the pre-installed firmware matches your site-specific LS2100 configuration.
-
What is the function of the alphanumeric display on the board face?
This display provides real-time error codes and status updates. During the start-up sequence, it tracks the processor's initialization steps and alerts the operator to specific communication or logic failures through predefined hex codes.
-
How does this board handle "Watchdog" safety functions?
The DS200DSPCH1A incorporates an independent watchdog timer circuit. If the DSP freezes or enters an infinite loop, the watchdog automatically resets the processor and forces the starter system into a safe state to prevent uncontrolled gate firing.
-
Is this board compatible with both Gas and Steam turbine static starters?
The DS200DSPCH1A primarily supports the LS2100 series used in gas turbine starting applications. However, compatibility depends on the specific bridge configuration. Always check your system's elementary drawings to confirm the part number matches your drive core requirements.
Return policy
We aim to provide reliable products and a smooth purchasing experience. If there is a problem with your order, please contact us and we will assist according to our Refund Policy.
Shipping
We provide international shipping options to meet different delivery requirements. Please review details regarding methods and timelines in our Shipping Policy.
Warranty
We provide a 12-month warranty for all products, subject to normal use and proper installation.
You may also like
Product Guide
What is an Interposing Relay in a PLC System?
What is an Interposing Relay in a PLC System?
Rockwell CompactLogix 5380 Controller: Advancing Smart Manufacturing with Precision and Connectivity
Rockwell CompactLogix 5380 Controller: Advancing Smart Manufacturing with Precision and Connectivity