Yokogawa
F3CU04-1S | Yokogawa 4-loop Temperature Control and PID Module
Manufacturer: Yokogawa
Product No.: F3CU04-1S
Product Type: Temperature Control and PID Module
Product Origin: Japan,Singapore
Payment:T/T, Western Union
Weight: 800g
Shipping port: Xiamen
Warranty: 12 months
Product Overview
The Yokogawa F3CU04-1S is a 4-loop temperature control and PID module for the FA-M3 series. Each loop independently supports RTD, thermocouple, and DC voltage inputs with 200 ms sampling and ±0.1% accuracy. Advanced control modes include single loop, cascade, and two-input changeover, making it a complete temperature control solution integrated directly into the PLC rack.
Key Specifications
- Number of Control Loops: 4 independent loops
- Input Types: RTD, Thermocouple, DC Voltage (per channel configurable)
- Control Modes: Single loop, Cascade, Two-input changeover
- Sampling Period: 200 ms per loop
- Input Accuracy: ±0.1% of full scale
- Resolution: 0.1°C
- Output Type: Time-proportional (open collector)
- Alarm Types: 12 types (upper/lower limits, deviation, range alarms)
- Alarm Outputs: 4 points per loop (alarms 1 & 2 have input relays)
- Alarm Delay Timer: Yes
- Current Consumption: 470 mA at 5V DC
- Mounting: Occupies 2 slots, horizontal orientation only
- Dimensions: 58(W) × 100(H) × 106.1(D) mm
- Weight: 350 g
Compatibility & Applications
Compatible with all FA-M3 base modules (occupies 2 consecutive slots). Perfect for plastic extrusion temperature control, heat treatment furnaces, chemical reactor temperature regulation, HVAC multi-zone control, and food processing ovens requiring precise multi-loop PID control.
FAQ
- Q: Does each loop need external power? A: No, the module is powered entirely from the FA-M3 backplane (470 mA at 5V DC).
- Q: Can I use different sensor types per loop? A: Yes, each of the 4 loops is independently configurable for RTD, TC, or DC voltage.
- Q: What is the output type? A: Time-proportional open collector output for driving external SSRs or contactors.
- Q: Does it support auto-tuning? A: Yes, the module supports PID auto-tuning for each independent loop.
Installation Guide
- Power off the FA-M3 system.
- Reserve 2 consecutive horizontal slots in the base module.
- Install F3CU04-1S in horizontal orientation only (vertical installation not supported).
- Connect temperature sensors and output devices to the two 18-point terminal blocks.
- Configure input types, PID parameters, and alarm setpoints via WideField3.
- Restore power and verify temperature readings and control outputs.
Selection Tips
- Use F3CU04-1S for multi-loop temperature control (up to 4 zones) within the FA-M3 rack.
- For 4 loops with enhanced features, F3CU04-0S is the successor/replacement model.
- Ensure the module is mounted horizontally; vertical orientation will cause inaccurate readings.
- Allow 30 minutes warm-up time before critical control operations.
Return policy
We aim to provide reliable products and a smooth purchasing experience. If there is a problem with your order, please contact us and we will assist according to our Refund Policy.
Shipping
We provide international shipping options to meet different delivery requirements. Please review details regarding methods and timelines in our Shipping Policy.
Warranty
We provide a 12-month warranty for all products, subject to normal use and proper installation.
You may also like