  • Manufacturer: Honeywell

  • Product No.: FC-TSRO-08UNI

  • Product Type: Field Termination Assembly

  • Product Origin: USA

  • Payment:T/T, Western Union

  • Weight: 1900g

  • Shipping port: Xiamen

  • Warranty: 12 months

Special offer ends!
00 :
00 :
00

Honeywell FC-TSRO-08UNI Safe Relay Output FTA

The Honeywell FC-TSRO-08UNI is an 8-channel safe relay output field termination assembly for Honeywell Safety Manager systems. It provides potential-free relay contacts for versatile industrial control with individual channel diagnostics.

Key Specifications

  • Model: FC-TSRO-08UNI
  • Type: Safe Relay Output FTA
  • Channels: 8 independent relay outputs
  • Contact Type: Changeover (NO/NC)
  • Contact Material: Silver-cadmium oxide (AgCdO)
  • Max Output Current: 5 A per channel
  • Max Output Voltage: 250 V AC / 300 V DC
  • Max Switched Load: 1250 VA / 150 W at 30 V DC
  • Input Voltage: 24 V DC nominal
  • Input Current: 27 mA typical at 24 V DC
  • Switching Frequency: 20 Hz maximum
  • Isolation: 4000 V AC (coil to contact); 1000 V AC (contact to contact)
  • Fuse: 5 A (Schurter 0001.2511, 5x20 mm)
  • Operating Temperature: -40°C to +70°C
  • Dimensions: 195 x 70 x 60 mm
  • Approvals: CE, TUV, UL, CSA, FM

FAQ

Q: How many relay channels are available?
A: 8 independent channels with NO/NC changeover contacts.

Q: What is the maximum switching capacity?
A: 5 A per channel, up to 250 V AC / 300 V DC.

Q: Does it support SIL-rated applications?
A: Yes, designed for Safety Manager SIL-rated systems.

Installation Guide

  1. Mount on DIN EN TS32/TS35 x 7.5 rail (196 mm required).
  2. Wire field loads to screw terminals (max 2.5 mm², torque 0.5 Nm).
  3. Connect SICC cable to corresponding digital output module.
  4. Verify fuse integrity and contact operation per channel.

Selection Tips

  • Match contact rating to load requirements (inductive/resistive).
  • Account for derating: 5 A at 25°C to 3.5 A at 70°C.
  • For safety loops, verify SIL compatibility with system architecture.
Return policy

​We aim to provide reliable products and a smooth purchasing experience. If there is a problem with your order, please contact us and we will assist according to our Refund Policy.

Shipping

We provide international shipping options to meet different delivery requirements. Please review details regarding methods and timelines in our Shipping Policy.

Warranty

We provide a 12-month warranty for all products, subject to normal use and proper installation.

You may also like