GE Fanuc
GE Fanuc PACSystems RX3i Analog Input Module IC694ALG220
Manufacturer: GE Fanuc
Product No.: IC694ALG220
Product Type: PACSystems RX3i Analog Input Module
Product Origin: USA
Payment:T/T, Western Union
Weight: 110g
Shipping port: Xiamen
Warranty: 12 months
Product Overview
Configured for precise voltage signal acquisition in PACSystems RX3i networks, the GE Fanuc IC694ALG220 (IC694ALG220 Analog Input Module) provides direct physical/electrical execution. This hardware component accepts 4 unipolar analog input channels to interface directly with field transmitters generating continuous voltage potentials. The module converts these incoming physical signals into discrete 12-bit binary values mapped across internal system registers.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | IC694ALG220 |
| Brand | GE Fanuc (PACSystems RX3i) |
| Module Type | Analog Input Module |
| Origin | United States |
| Weight | 0.26 kg |
| Dimensions | 3.2 cm x 14.1 cm x 11.5 cm |
| Operating Temp | 0 to 60 deg C |
| Power Consumption | 27 mA at 5 VDC from backplane, 98 mA at 24 VDC from backplane |
| Channels | 4 single-ended, unipolar |
| Signal Range | 0 to 10 VDC |
| Update Rate | 5 ms per selected channel |
| Converter Resolution | 12-bit binary precision |
I/O Density Scaling and Backplane Bus Communications
The hardware form factor matches standard single-slot dimensions, facilitating efficient I/O density scaling inside standard RX3i backplane rack structures. Module parameters and conversion updates are processed in strict synchronization with the CPU execution cycle via configured backplane bus communication velocity frameworks. The internal diagnostic subsystem evaluates voltage scaling boundaries, confirming that data pathways remain consistent with system-wide firmware flash compatibility tables.
Frequently Asked Questions
Q: Does this module require an external 24 VDC loop power supply for input channel operation?
A: No. The internal logic and the signal conditioning networks derive all required operational current straight from the 5 VDC and 24 VDC power rails of the RX3i chassis backplane.
Q: How does the module react if an input signal voltage exceeds the maximum 10 VDC boundary limit?
A: The internal converter registers will latch at the maximum count value ($4095$ in decimal). Prolonged overvoltage spikes up to a continuous 30 VDC will not damage the module circuits, but values above this limit breach structural isolation.
Field Installation Guidelines
- Shield Grounding Framework: Connect all signal wires using twisted-pair cables with overall foil shielding. Terminate the drain wire element at a clean single-point panel ground bus inside the enclosure.
- Chassis Attachment Procedure: Insert the module into the targeted slot by aligning the upper and lower guide rails. Pivot the assembly firmly into the backplane until the faceplate latch engages securely.
- Signal Cable Isolation: Maintain physical isolation distances between low-voltage analog input conductors and high-power AC motor starters or inductive power circuits to minimize signal distortion.
Return policy
We aim to provide reliable products and a smooth purchasing experience. If there is a problem with your order, please contact us and we will assist according to our Refund Policy.
Shipping
We provide international shipping options to meet different delivery requirements. Please review details regarding methods and timelines in our Shipping Policy.
Warranty
We provide a 12-month warranty for all products, subject to normal use and proper installation.