Honeywell 2MLL-C42A 2-Channel RS-422 Serial Communication Module
Manufacturer: Honeywell
Product No.: 2MLL-C42A
Product Type: Communication Module
Product Origin: USA
Payment:T/T, Western Union
Weight: 1700g
Shipping port: Xiamen
Warranty: 12 months
Product Overview
The Honeywell 2MLL-C42A is a 2-channel RS-422 serial communication module for the MasterLogic-200 (ML200) PLC system. It enables high-speed, noise-immune serial data exchange between the ML200 CPU and third-party devices such as barcode scanners, weigh scales, variable frequency drives, and legacy RS-422 instrumentation. With isolated channels and support for multiple protocols including Modbus RTU/ASCII, it serves as the backbone for integrated automation architectures.
Key Specifications
- Product Type: Serial Communication Module (RS-422)
- Series: MasterLogic-200 / ML200
- Channels: 2 (RS-422)
- Isolation: Channel-to-channel and channel-to-internal logic isolation
- Supported Protocols: Modbus RTU, Modbus ASCII, dedicated protocol, user-defined protocol
- Baud Rate: 300 bps to 115,200 bps (software selectable)
- Data Format: 7/8 data bits, 1/2 stop bits, odd/even/none parity
- Transmission Distance: Up to 1,200 meters (at 9,600 bps)
- Connection: 9-pin D-sub connector (per channel)
- Current Consumption: 40 mA (from 5V internal bus)
- External Power: DC 24V (20.4–28.8V) for interface circuits
- Dimensions (W x H x D): 27.4 mm x 90 mm x 70 mm
- Weight: Approx. 90 g
- Operating Temperature: 0°C to +55°C
Features & Benefits
- Dual isolated RS-422 channels — run two independent serial networks from one module, reducing communication module count by 50%
- Long-distance transmission — RS-422 differential signaling supports cable runs up to 1,200 meters, ideal for warehouse and material handling applications
- Multi-protocol support — built-in Modbus RTU/ASCII master and slave functions eliminate the need for custom protocol programming
- Galvanic isolation — protects the CPU from ground potential differences between the PLC cabinet and remote field devices
- High-speed 115.2 kbps — enables real-time data exchange with high-speed barcode readers and servo controllers
Typical Applications
- Barcode scanner and RFID reader integration on packaging lines
- Weigh scale and load cell indicator communication in batching systems
- VFD parameter read/write for pump and fan control
- Legacy PLC and DCS gateway integration via Modbus RTU
- Remote terminal unit (RTU) communication in water/wastewater SCADA
- Robotic controller serial interface for coordinate data exchange
Installation Guide
- Install in I/O slot — mount the 2MLL-C42A in any available I/O slot of the ML200 main or expansion base.
- Connect 24V external power — wire DC 24V to the external power terminals for the RS-422 interface drivers.
- Wire RS-422 network — connect TX+, TX-, RX+, and RX- to the field device using twisted-pair shielded cable (minimum 0.5 mm²). Ground the shield at one end only.
- Configure protocol in SoftMaster — set baud rate, data format, and protocol type (Modbus RTU master/slave or dedicated protocol) in the CPU parameter settings.
- Test communication — use the SoftMaster monitor function to verify data register exchange with the connected device.
FAQ
Q: What is the difference between 2MLL-C42A and 2MLL-C42B?
A: The 2MLL-C42A is the standard RS-422 2-channel module. The 2MLL-C42B is a variant with potentially different connector orientation or conformal coating. Verify your system BOM for the exact suffix required. Electrical specifications are identical.
Q: Can I use this for RS-485 networks?
A: RS-422 is not directly interchangeable with RS-485 for multi-drop master-slave networks. For RS-485 applications, use the 2MLL-C42B or an external RS-422 to RS-485 converter.
Q: What is the maximum number of devices per channel?
A: RS-422 supports one driver and up to 10 receivers per channel. For multi-drop Modbus networks with >10 devices, use RS-485 topology instead.
Q: Does this module support protocol conversion?
A: The 2MLL-C42A supports Modbus RTU/ASCII natively. For protocol conversion (e.g., Modbus to Profibus), use the 2MLL-PMEA (Profibus Master) or 2MLL-PSEA (Profibus Slave) modules.
Selection Tips
- Select 2MLL-C42A for point-to-point or limited multi-drop RS-422 serial communication with drives, scales, and barcode readers.
- If you need RS-232C instead of RS-422, choose 2MLL-C22A (2-channel RS-232C).
- For mixed RS-232C and RS-422 on one module, select 2MLL-CH2A (1ch RS-232C + 1ch RS-422).
- Always use twisted-pair shielded cable for RS-422 runs >100 meters to prevent electromagnetic interference.
Return policy
We aim to provide reliable products and a smooth purchasing experience. If there is a problem with your order, please contact us and we will assist according to our Refund Policy.
Shipping
We provide international shipping options to meet different delivery requirements. Please review details regarding methods and timelines in our Shipping Policy.
Warranty
We provide a 12-month warranty for all products, subject to normal use and proper installation.