Honeywell
Honeywell 2MLR-AC23 Redundant Power Supply Module AC 220V 8.5A
Manufacturer: Honeywell
Product No.: 2MLR-AC23
Product Type: Redundant Power Supply Module
Product Origin: USA
Payment:T/T, Western Union
Weight: 1300g
Shipping port: Xiamen
Warranty: 12 months
Product Overview
The Honeywell 2MLR-AC23 is a high-capacity redundant power supply module for the MasterLogic-200R (ML200R) PLC system. It accepts AC 220V input and delivers regulated DC 5V at 8.5A to power redundant CPU racks, I/O modules, and communication interfaces. With active-active load sharing and hot-swap capability, it ensures continuous power delivery for the most demanding critical control applications in power generation, oil & gas, and chemical processing.
Key Specifications
- Product Type: Redundant Power Supply Module (High Capacity)
- Series: MasterLogic-200R (Redundant)
- Input Voltage: AC 220V (200–240V range)
- Output Voltage: DC 5V (regulated ±2%)
- Output Current: 8.5A
- Redundancy Type: Active-Active (parallel sharing)
- Switchover Time: Zero (seamless failover)
- Efficiency: >85%
- Protection: Overvoltage, overcurrent, short-circuit, thermal shutdown
- Run Contact: SPDT relay contact (250V AC / 2A) for status indication
- Hot-Swappable: Yes
- Dimensions (W x H x D): 122 mm x 35 mm x 100 mm
- Weight: Approx. 0.45 kg
- Operating Temperature: 0°C to +55°C
- Certifications: CE, RoHS
Features & Benefits
- 8.5A high capacity — 55% more power than the 5.5A AC22, supporting fully loaded 12-slot redundant racks with high-density I/O and multiple communication modules
- 220V AC input for international sites — designed for European, Asian, and Australian mains voltage standards, eliminating step-down transformers
- Active-active redundancy — dual 2MLR-AC23 modules share the load; failure of one supply results in instantaneous, bumpless transfer to the surviving unit
- Hot-swap maintenance — defective power supplies can be extracted and replaced while the process continues to run, maximizing system availability
- Built-in run contact — dry contact output interfaces with BMS, SCADA, or annunciator panels for immediate power fault notification
Typical Applications
- Large steam turbine control and protection systems
- Petrochemical refinery safety instrumented systems (SIS)
- Nuclear power plant auxiliary control
- Offshore platform topside process control
- Pharmaceutical multi-reactor batch control
- Any fully loaded 12-slot ML200R rack requiring maximum power margin
Installation Guide
- Confirm mains voltage — verify your site provides AC 220V (200–240V). For AC 110V sites, use 2MLR-AC13 (8.5A) instead.
- Install in redundant power slots — mount two 2MLR-AC23 modules in the dedicated power supply slots of the ML200R main base (2MLR-M02P or 2MLR-M06P).
- Wire independent feeds — connect each power supply to a separate AC circuit breaker and distribution panel to achieve true power source diversity.
- Connect earth ground — bond the PE terminal to the cabinet earth bus with 2.5 mm² wire.
- Wire run contacts — connect the SPDT relay contacts to your alarm system or PLC diagnostic input for remote monitoring.
- Test failover — energize both supplies, confirm load sharing, then remove one supply and verify the second maintains 5V output without CPU fault.
FAQ
Q: What is the difference between 2MLR-AC23 and 2MLR-AC22?
A: The 2MLR-AC23 provides 8.5A output. The 2MLR-AC22 provides 5.5A output. Both accept AC 220V input. Choose AC23 for fully loaded 12-slot racks; choose AC22 for 2-slot and 6-slot racks.
Q: Can I mix AC22 and AC23 in the same rack?
A: No. Honeywell recommends using identical power supply models in redundant pairs to ensure equal load sharing and prevent circulating currents.
Q: Is this compatible with non-redundant ML200 bases?
A: No. The 2MLR-AC23 is mechanically and electrically designed for ML200R redundant bases only (2MLR-M02P, 2MLR-M06P).
Q: What is the efficiency and heat dissipation?
A: At >85% efficiency, a fully loaded 2MLR-AC23 dissipates approximately 25–30W as heat. Ensure 50 mm clearance above and below the module for convective cooling.
Selection Tips
- Select 2MLR-AC23 for AC 220V sites with fully loaded 12-slot redundant racks.
- For smaller racks (2-slot or 6-slot), the 2MLR-AC22 (5.5A) is more cost-effective.
- For AC 110V sites, choose 2MLR-AC13 (8.5A) or 2MLR-AC12 (5.5A).
- Always install two identical power supplies per rack — never run redundant systems with a single supply.
- Calculate your total 5V bus load (CPU + I/O + communication modules) before ordering; a 12-slot rack with high-density I/O typically requires 8.5A.
Return policy
We aim to provide reliable products and a smooth purchasing experience. If there is a problem with your order, please contact us and we will assist according to our Refund Policy.
Shipping
We provide international shipping options to meet different delivery requirements. Please review details regarding methods and timelines in our Shipping Policy.
Warranty
We provide a 12-month warranty for all products, subject to normal use and proper installation.
You may also like
Product Guide
Mitigating SCADA Performance Drops During Shift Transitions
Mitigating SCADA Performance Drops During Shift Transitions
Optimizing SCADA Performance: Why Remote Clients Experience Lag
Optimizing SCADA Performance: Why Remote Clients Experience Lag