Honeywell
Honeywell 900H02-0202 ControlEdge HC900 24VDC 16-Channel Sinking Digital Output Module
Manufacturer: Honeywell
Product No.: 900H02-0202
Product Type: DC Digital Output Module
Product Origin: USA
Payment:T/T, Western Union
Weight: 1500g
Shipping port: Xiamen
Warranty: 12 months
Product Overview
The Honeywell 900H02-0202 is a 16-channel 24VDC sinking digital output module for the Honeywell ControlEdge HC900 PLC system. This module provides high-side switching (current sinking) outputs for controlling DC-powered field devices, with overcurrent protection organized in groups for reliable industrial operation.
Key Specifications
- Channels: 16 digital outputs
- Output Voltage: 6.5–32 VDC
- Output Type: Sinking (high-side switching)
- Current per Channel: 1 A continuous
- Maximum Module Current: 8 A total
- Power Consumption: 340 mA @ 5VDC (from rack backplane)
- Response Time: 6 ms ON / 6 ms OFF
- Channel Grouping: 2 groups of 8 channels
- Overcurrent Protection: Per group (8 channels per group)
- Operating Temperature: 0°C to 60°C (32°F to 140°F)
- Status Indicators: Green LED per channel, scan/fault LEDs
Compatibility
The 900H02-0202 is compatible with:
- Racks: All HC900 4-slot, 8-slot, and 12-slot racks
- Processor Modules: All 900CP1 series CPMs
- Terminal Blocks: Compatible with barrier and Euro-style terminal blocks
Installation Guide
- Power down: De-energize the HC900 rack before module installation.
- Insert module: Install the 900H02-0202 into any available I/O slot.
- Secure module: Lock the retention lever to ensure proper backplane connection.
- Wire outputs: Connect field device positive (+) to the output terminal and negative (-) to the COM terminal for each group.
- Apply power: Energize the rack and verify green LEDs illuminate when outputs are commanded ON.
- Test overcurrent: Verify that a short circuit on any channel disables only its group of 8 channels.
FAQ
Q: What happens during an overcurrent event?
A: If any channel in a group of 8 experiences a short circuit, the entire group is switched off. Power cycling is not required to reset the module.
Q: Can I mix sourcing and sinking outputs in the same rack?
A: Yes. The HC900 rack supports both 900H02-0202 (sinking) and 900H32-0302 (sourcing) modules simultaneously.
Q: What is the maximum inrush current?
A: The module supports 2A inrush current for 100 ms per channel.
Selection Tips
- Use the 900H02-0202 for DC sinking applications where field devices share a common positive supply.
- For sourcing applications (current sourcing to loads), select the 900H32-0302 32-channel module.
- Ensure total module current does not exceed 8A. Distribute high-current loads across multiple modules if necessary.
- Wire each group of 8 channels to a separate COM terminal for optimal fault isolation.
Standards & Certifications
- CE Marked
- UL Listed
- CSA Certified
- RoHS Compliant
Return policy
We aim to provide reliable products and a smooth purchasing experience. If there is a problem with your order, please contact us and we will assist according to our Refund Policy.
Shipping
We provide international shipping options to meet different delivery requirements. Please review details regarding methods and timelines in our Shipping Policy.
Warranty
We provide a 12-month warranty for all products, subject to normal use and proper installation.
You may also like
Product Guide
Mitigating SCADA Performance Drops During Shift Transitions
Mitigating SCADA Performance Drops During Shift Transitions
Optimizing SCADA Performance: Why Remote Clients Experience Lag
Optimizing SCADA Performance: Why Remote Clients Experience Lag