Honeywell
Honeywell 900R08-0200 8-Slot I/O Rack (Non-Redundant)
Manufacturer: Honeywell
Product No.: 900R08-0200
Product Type: I/O Rack
Product Origin: USA
Payment:T/T, Western Union
Weight: 1700g
Shipping port: Xiamen
Warranty: 12 months
Product Overview
The Honeywell 900R08-0200 is an 8-slot I/O rack with non-redundant power designed for the ControlEdge HC900 controller family. This compact, cost-effective chassis provides 8 module slots for analog, digital, universal, and communication I/O modules, making it ideal for medium-scale process automation where power redundancy is not required. With IRUP support and rugged aluminum construction, the 900R08-0200 delivers reliable performance in a space-efficient form factor.
Key Features
- 8 I/O module slots for medium-density automation
- Non-redundant power design — single power supply slot for cost savings
- IRUP capable — supports hot-swapping of I/O modules
- Universal module compatibility — all HC900 I/O types supported
- Compact design — saves cabinet space
- DIN rail or panel mounting
- Passive cooling — no fans required
Technical Specifications
- Model: 900R08-0200
- Product Type: 8-Slot I/O Rack (Non-Redundant Power)
- Series: ControlEdge HC900
- Number of Slots: 8 I/O slots + single power supply slot
- Power Support: Non-redundant (single power supply)
- Dimensions (H × W × D): 137 × 419 × 152 mm (5.4" × 16.5" × 6.0")
- Weight: Approx. 1.44 kg (3.2 lbs)
- Mounting: DIN rail or panel mount
- Operating Temperature: 0°C to +60°C
- Storage Temperature: −40°C to +85°C
- Humidity: 5% to 95% RH (non-condensing)
- Construction: High-grade aluminum
- Certifications: CE, UL, CSA
Typical Applications
- Medium-scale process control systems
- Manufacturing automation
- Water and wastewater treatment
- Building automation and HVAC control
- Non-safety applications where power redundancy is not critical
FAQ
Q: How many slots does the 900R08-0200 have?
A: It has 8 I/O module slots plus a single power supply slot and an I/O scanner slot.
Q: Does it support redundant power?
A: No. For redundant power, use the 900R08R-0200.
Q: What is the maximum I/O capacity?
A: With 32-channel high-density modules, up to 256 I/O points (8 slots × 32 channels) per rack.
Q: Can I upgrade from 900R08-0200 to redundant power later?
A: No. The rack backplane determines power redundancy capability. To add redundancy, you must replace the entire rack with a 900R08R-0200.
Installation Guide
- Mounting: Attach the rack to a DIN rail or panel using the provided mounting hardware.
- Power Supply: Install a single compatible power supply (e.g., 900P01-0201) in the power slot.
- Scanner: Insert the I/O scanner module (900S75-0360-00).
- I/O Modules: Insert modules into available slots, pressing firmly until retention clips engage.
- Grounding: Connect rack ground to cabinet earth bus.
- System Check: Power on and verify module recognition in Hybrid Control Designer.
Selection Tips
- Select the 900R08-0200 for cost-effective medium I/O density where power redundancy is not required.
- If power redundancy is needed, upgrade to the 900R08R-0200.
- For larger systems, consider the 900R12-0200 (12-slot).
- For small systems, the 900R04-0300 (4-slot) may be sufficient.
- Verify total power budget against the single power supply rating.
Return policy
We aim to provide reliable products and a smooth purchasing experience. If there is a problem with your order, please contact us and we will assist according to our Refund Policy.
Shipping
We provide international shipping options to meet different delivery requirements. Please review details regarding methods and timelines in our Shipping Policy.
Warranty
We provide a 12-month warranty for all products, subject to normal use and proper installation.
You may also like
Product Guide
Mitigating SCADA Performance Drops During Shift Transitions
Mitigating SCADA Performance Drops During Shift Transitions
Optimizing SCADA Performance: Why Remote Clients Experience Lag
Optimizing SCADA Performance: Why Remote Clients Experience Lag