Skip to product information
Honeywell FS-16DI-RL Relay Input Terminal Board

Honeywell

Honeywell FS-16DI-RL Relay Input Terminal Board

In stock
  • Manufacturer: Honeywell

  • Product No.: FS-16DI-RL

  • Product Type: Terminal Board

  • Product Origin: USA

  • Payment:T/T, Western Union

  • Weight: 300g

  • Shipping port: Xiamen

  • Warranty: 12 months

Special offer ends!
00 :
00 :
00

Product Overview

The Honeywell FS-16DI-RL is a 16-channel digital input module designed for Honeywell Safety Manager systems. It provides reliable acquisition of discrete signals from field devices in safety-critical industrial applications. With low-power consumption design and wide voltage tolerance, this module ensures accurate status monitoring for emergency shutdown systems, process interlocks, and safety instrumented systems.

Key Features

  • 16 Digital Input Channels: High-density discrete signal acquisition
  • Wide Voltage Range: 10–30 VDC input tolerance for flexible field device compatibility
  • Low Power Consumption: Energy-efficient design reduces system power requirements
  • Opto-Isolated Inputs: Electrical isolation protects internal circuitry from field transients
  • Status LEDs: Per-channel indication for quick diagnostics
  • Compact Design: Standard 4TE module width for efficient chassis utilization

Technical Specifications

  • Model: FS-16DI-RL
  • Type: 16-Channel Digital Input Module
  • Input Type: Digital, discrete signals
  • Number of Channels: 16 inputs
  • Voltage Range: 10–30 VDC
  • Input Current: Low-power consumption design
  • Isolation: Opto-isolated per channel
  • Module Width: 4 TE (20.32 mm / 0.8 in)
  • Operating Temperature: -40°C to +70°C

Installation Guide

  1. Chassis Insertion: Slide module into designated slot until flush with chassis front
  2. Flat Cable Connection: Connect horizontal IO bus flat cable to module front connector
  3. Field Termination: Use compatible FTA (e.g., FC-TSDI-1624) for field wiring interface
  4. Address Assignment: Module address determined by slot position—no jumpers or switches needed
  5. Hot-Swap: Module can be replaced with power on; verify process impact before removal

FAQ

Q: Does this module require an FTA?
A: Yes. The FS-16DI-RL is the I/O module installed in the chassis. Field wiring connects via a compatible Field Termination Assembly (FTA) such as FC-TSDI-1624.

Q: Can inputs from different voltage sources be mixed?
A: All 16 channels share common configuration. Verify field device voltage compatibility before installation.

Q: What is the replacement procedure?
A: Disconnect flat cable, loosen screws, slide out old module, insert new module, reconnect flat cable. Address is automatic based on slot position.

Selection Tips

  • Verify voltage compatibility with field devices (10–30 VDC range)
  • Pair with appropriate FTA based on wiring requirements (screw terminals, wire gauge)
  • For SIL-rated applications, ensure complete safety loop calculation includes this module
Return policy

​We aim to provide reliable products and a smooth purchasing experience. If there is a problem with your order, please contact us and we will assist according to our Refund Policy.

Shipping

We provide international shipping options to meet different delivery requirements. Please review details regarding methods and timelines in our Shipping Policy.

Warranty

We provide a 12-month warranty for all products, subject to normal use and proper installation.