GE Fanuc
IC200ALG326 Analog Output Modules GE VersaMax
Manufacturer: GE Fanuc
Product No.: IC200ALG326
Product Type: Analog Output Modules
Product Origin: USA
Payment:T/T, Western Union
Weight: 110g
Shipping port: Xiamen
Warranty: 12 months
The GE IC200ALG326, also cataloged as the IC200ALG326 Analog Output Module, operates as a dedicated hardware component for multi-channel current signal generation within VersaMax I/O station platforms. The module interfaces with the station backplane to convert digital data frames into isolated analog current loops across field instruments. It regulates external loop actuators by driving continuous 4-20 mA control pathways derived directly from cyclic processor register updates.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | IC200ALG326 |
| Brand | GE |
| Origin | United States |
| Weight | 0.18 kg |
| Dimensions | 66.8 mm x 128 mm x 50.2 mm |
| Operating Temp | 0 to 60 deg C |
| Power Consumption | 120 mA maximum at 5 VDC from backplane / 100 mA maximum at 24 VDC external |
| Output Channels | 8 single-ended current channels |
| Signal Range | 4-20 mA |
| Resolution | 13 bits |
| External Power Supply | 18 to 30 VDC field excitation voltage |
I/O Density Scaling
The module supports local I/O density scaling transitions by accommodating 8 high-resolution current loops on a uniform physical carrier footprint. Integrated logic blocks communicate over the local bus plane without causing capacitive cross-talk or thermal overloading between adjacent hardware channels. Maintained firmware flash compatibility within the VersaMax controller family coordinates deterministic signal update scheduling, suppressing execution latencies during multi-point synchronous scanning sequences.
Frequently Asked Questions
Q: Does the IC200ALG326 module support extraction or live replacement when the base rack is energized?
A: No, hot-swapping the hardware while backplane power is actively supplied is prohibited. The input lines must be isolated before insertion or extraction to prevent signal line damage or module communication errors.
Q: How does the hardware indicate a loss of the external 24 VDC field excitation supply?
A: A missing or degraded field supply drops the module into an active fault profile, reporting a diagnostic message word to the CPU while the localized LED matrix alters state.
Q: What is the behavior of the current output channels upon a localized loss of backplane logic power?
A: If backplane logic power is interrupted, the output channels default to 0 mA or assume their low-scale fail-safe positions immediately.
Field Installation Guidelines
Mount the unit vertically onto a leveled 35 mm DIN-rail base utilizing the compatible VersaMax terminal carrier frame. Retain a minimum open clearance footprint of 50 mm above and below the module ventilation openings to secure proper convective thermal heat sink dissipation. Route all 4-20 mA current signaling lines using dedicated twisted, shielded instrumentation pairs isolated from high-voltage motor or distribution conductors. Secure the field cable shield drains to a single-point panel ground bar to maintain signal resolution and isolate the loops from common-mode electrical noise.
Return policy
We aim to provide reliable products and a smooth purchasing experience. If there is a problem with your order, please contact us and we will assist according to our Refund Policy.
Shipping
We provide international shipping options to meet different delivery requirements. Please review details regarding methods and timelines in our Shipping Policy.
Warranty
We provide a 12-month warranty for all products, subject to normal use and proper installation.