Product Summary

The GE Fanuc IC200UDR140 is a VersaMax Micro 40-Point PLC with 24 discrete 24VDC inputs and 16 relay outputs. It operates from 120/240VAC and features high-speed counter inputs up to 100 kHz.

Core Specifications

  • Model Number: IC200UDR140
  • Type: VersaMax Micro 40-Point PLC
  • Inputs: 24 discrete inputs, 24VDC
  • Outputs: 16 relay outputs, 2A @ 24VDC/250VAC
  • High-Speed Counter: 4 inputs, up to 100 kHz
  • Power Supply: 120/240VAC
  • User Power: 24VDC output, 435 mA max
  • Serial Port: RS-232
  • Programming: Proficy Machine Edition 5.7+
  • Memory: Requires IC200ACC414 battery
  • Manufacturer: GE Fanuc / Emerson

Key Features

  • 24 inputs configurable as standard or high-speed counter
  • 16 relay outputs with 2A rating
  • 120/240VAC power supply eliminates external DC power
  • Online programming without stopping
  • Expandable up to 170 points

Environmental Limits

  • Operating Temperature: -20°C to +60°C
  • Humidity: 5% to 95% RH, non-condensing

Frequently Asked Questions

What is the IC200UDR140 used for?

Compact PLC for small to medium automation with 24 inputs, 16 relay outputs, and 120/240VAC power.

What is the difference between IC200UDR140 and IC200UDR040?

IC200UDR140 uses 120/240VAC. IC200UDR040 uses 24VDC. Both have 24 inputs / 16 outputs.

What is the difference between IC200UDR140 and IC200UDR164?

IC200UDR140 has 24 in / 16 out. IC200UDR164 has 40 in / 24 out with same AC power.

Installation Guide

Safety Precautions

  • De-energize AC power before installation
  • Use ESD protection
  • Install IC200ACC414 battery

Step-by-Step

  1. Mount on DIN rail
  2. Connect 120/240VAC power
  3. Wire 24 inputs and 16 outputs
  4. Connect RS-232 programming cable
  5. Power up and verify LEDs

Selection Tips

  • For DC power, select IC200UDR040
  • For more I/O, select IC200UDR164
  • For transistor outputs, select IC200UDD140
  • Do not exceed 2A per relay output

Related Part Numbers

  • IC200UDR040 — 24 In / 16 Relay Out, 24VDC
  • IC200UDR140 — 24 In / 16 Relay Out, 120/240VAC (this part)
  • IC200UDR164 — 40 In / 24 Relay Out, 120/240VAC
  • IC200UDD140 — 24 In / 16 DC Out, 120/240VAC
  • IC200ACC414 — Battery
Return policy

​We aim to provide reliable products and a smooth purchasing experience. If there is a problem with your order, please contact us and we will assist according to our Refund Policy.

Shipping

We provide international shipping options to meet different delivery requirements. Please review details regarding methods and timelines in our Shipping Policy.

Warranty

We provide a 12-month warranty for all products, subject to normal use and proper installation.

You may also like