GE Fanuc
IC693CBL300 | GE Fanuc Series 90-30 Standard Wye (Y) Expansion Cable
Manufacturer: GE Fanuc
Product No.: IC693CBL300
Product Type: Cable
Product Origin: USA
Payment:T/T, Western Union
Weight: 100g
Shipping port: Xiamen
Warranty: 12 months
Product Summary
The IC693CBL300 is a standard Wye (Y) cable used for interconnecting baseplates in Series 90-30 PLC expansion or remote I/O configurations. It serves as a jumper cable for daisy-chaining multiple baseplates in multi-rack systems.
Core Specifications
- Model Number: IC693CBL300
- Cable Type: Standard Wye (Y) Expansion Cable
- Length: 1 m (3.28 ft)
- Connectors: 25-pin D-subminiature male on one end, 25-pin D-subminiature female on the other (with Wye configuration for branching)
- Cable Construction: Shielded, twisted-pair cable (Belden 8107 or equivalent recommended)
- Application: Interconnection of expansion and remote baseplates
Electrical & Interface Characteristics
- Function: Provides parallel I/O bus expansion between baseplates
- Maximum System Configuration: Supports up to 8 baseplates (local + expansion/remote) depending on total cable length and power considerations
- Termination: Proper termination required at the end of the expansion bus (see IC693ACC307 Bus Terminator)
Installation Guide
- Power off the PLC system before connecting or disconnecting expansion cables.
- Connect the male end of the cable to the expansion port on the CPU baseplate or previous expansion baseplate.
- Connect the female end to the next baseplate in the chain.
- For Wye configurations, use the branching legs to connect multiple baseplates as required.
- Ensure total cable length does not exceed system limits and install a bus terminator at the final baseplate.
- Verify proper grounding and shielding to minimize noise.
Selection Guidelines
- Use IC693CBL300 for standard short-distance baseplate interconnections (1 m).
- For longer distances, select IC693CBL301 (2 m) or IC693CBL302 (15 m with built-in terminator).
- Always calculate total expansion cable length and power budget when designing multi-rack systems.
- Use IC693ACC307 Bus Terminator at the end of the I/O bus.
Return policy
We aim to provide reliable products and a smooth purchasing experience. If there is a problem with your order, please contact us and we will assist according to our Refund Policy.
Shipping
We provide international shipping options to meet different delivery requirements. Please review details regarding methods and timelines in our Shipping Policy.
Warranty
We provide a 12-month warranty for all products, subject to normal use and proper installation.