Skip to product information
SARM55W | Yokogawa Terminal Board (Wet Contact Output)

Yokogawa

SARM55W | Yokogawa Terminal Board (Wet Contact Output)

10 left
  • Manufacturer: Yokogawa

  • Product No.: SARM55W

  • Product Type: Relay Output Terminal Board

  • Product Origin: USA

  • Payment:T/T, Western Union

  • Weight: 1600g

  • Shipping port: Xiamen

  • Warranty: 12 months

Special offer ends!
00 :
00 :
00

Product Overview

The SARM55W is a mechanical relay wet contact output terminal board for the Yokogawa CENTUM VP FIO subsystem. It provides 32 wet contact output points and interfaces digital output modules (ADV551 / ADV561) to field devices that require powered contacts.

Key Features

  • 32 wet contact output points
  • M4 screw terminals
  • Supports single and dual-redundant configurations
  • Dual-line field power supply (per 16 points)
  • Compatible with AKB331 / AKB337 signal cables

Technical Specifications

  • Contact Points: 32
  • Contact Type: Wet contact output
  • Terminals: M4 screws
  • Maximum Load: 250 V AC 0.6 A, 30 V DC 0.6 A, 125 V DC 0.1 A per point
  • Minimum Load: 5 V, 10 mA
  • Internal Power: 24 V DC, max 0.65 A
  • Field Power Supply: Dual-line (per 16 points)
  • Compatible Modules: ADV551 (32-point), ADV561 (64-point)
  • Dimensions: 482.6 mm (W) × 177 mm (H) (4U)
  • Weight: Approx. 2.6 kg
  • Ambient Temperature: 0 to 50 °C

FAQ

  • What is the main difference from SARM55D? SARM55W provides wet contacts with field power supply; SARM55D is dry contact (NO only).
  • Does it support redundancy? Yes, single or dual-redundant configurations are supported.
  • What signal cables are used? AKB331 (32-point) or AKB337 (64-point).

Installation Guide

  1. Mount the board in a 19-inch rack (note the 4U height).
  2. Connect the AKB331 or AKB337 signal cable to the ADV551/ADV561 module.
  3. Wire field devices to the M4 terminals.
  4. Connect the dual-line field power supplies and internal 24 V DC power.
  5. Power up and verify wet contact operation.

Selection Tips

  • Select SARM55W when field devices require powered (wet) contacts.
  • Confirm the dual-line field power capacity meets your load requirements.
  • Check rack height (4U) before installation.
Return policy

​We aim to provide reliable products and a smooth purchasing experience. If there is a problem with your order, please contact us and we will assist according to our Refund Policy.

Shipping

We provide international shipping options to meet different delivery requirements. Please review details regarding methods and timelines in our Shipping Policy.

Warranty

We provide a 12-month warranty for all products, subject to normal use and proper installation.

You may also like