Skip to product information
Schneider BMXAMO0210 2-Ch Isolated High-Level Analog Output

Schneider

Schneider BMXAMO0210 2-Ch Isolated High-Level Analog Output

10 left
  • Manufacturer: Schneider

  • Product No.: BMXAMO0210

  • Product Type: Analog Output Module

  • Product Origin: USA

  • Payment:T/T, Western Union

  • Weight: 1600g

  • Shipping port: Xiamen

  • Warranty: 12 months

Special offer ends!
00 :
00 :
00

Product Overview

The Schneider Electric BMXAMO0210 is a 2-channel isolated high-level analog output module for the Modicon X80 platform. It provides configurable voltage and current outputs with 15-bit + sign resolution for precise actuator control.

  • Analogue Output Number: 2 isolated channels
  • Output Types: 0...20 mA, 4...20 mA, ±10 V
  • Analogue Output Resolution: 15 bits + sign
  • Conversion Time: ≤ 1 ms
  • Load Impedance: ≤ 600 Ω (current) / ≥ 1000 Ω (±10 V)
  • Measurement Error: ≤ 0.2 % FS (0...60 °C) / 0.1 % FS at 25 °C
  • Temperature Drift: 30 ppm/°C
  • Isolation Voltage: 750 V DC between channels; 1400 V DC channels to ground/bus
  • Detection: Open circuit (current ranges) / Short circuit (±10 V)
  • Fallback Mode: Configurable or predefined
  • Status LEDs: RUN (green), channel diagnostic (green), ERR (red), I/O (red)
  • Net Weight: 0.144 kg
  • Power Consumption: Typical 2.1 W at 24 V DC / 0.35 W at 3.3 V DC
  • Operating Temperature: 0...60 °C

Key Features

  • Channel isolation for improved signal integrity
  • Factory calibrated with low drift
  • Open-circuit and short-circuit detection
  • Compatible with Modicon M340 and M580

FAQ

  • What output ranges are available? 0-20 mA, 4-20 mA and ±10 V.
  • Is the module isolated? Yes, between channels and to the bus/ground.
  • What is the maximum conversion time? ≤ 1 ms.
  • Does it support fallback? Yes, configurable or predefined fallback modes.

Installation Guide

  1. Mount the module in an X80 rack slot and secure.
  2. Connect the 20-way terminal block.
  3. Wire loads observing load impedance limits for voltage or current mode.
  4. Configure output type and fallback behavior in the programming software.
  5. Check status LEDs and perform loop checks before process startup.

Selection Tips

  • Choose BMXAMO0210 for applications needing isolated analog outputs with fast response.
  • Verify load impedance matches the selected range (current ≤600 Ω, voltage ≥1 kΩ).
  • For higher channel count, consider 4-channel alternatives in the X80 family.
  • Use hardened (H) version for severe environmental conditions.
Return policy

​We aim to provide reliable products and a smooth purchasing experience. If there is a problem with your order, please contact us and we will assist according to our Refund Policy.

Shipping

We provide international shipping options to meet different delivery requirements. Please review details regarding methods and timelines in our Shipping Policy.

Warranty

We provide a 12-month warranty for all products, subject to normal use and proper installation.

You may also like