GE Fanuc
Series 90-30 CPU Module IC693CPU313 GE Fanuc
Manufacturer: GE Fanuc
Product No.: IC693CPU313
Product Type: Series 90-30 CPU Module
Product Origin: USA
Payment:T/T, Western Union
Weight: 110g
Shipping port: Xiamen
Warranty: 12 months
Product Overview
The GE Fanuc IC693CPU313, also cataloged as the IC693CPU313 CPU Module, operates as a dedicated hardware component for central processing and logic execution within Series 90-30 programmable logic controller platforms.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | IC693CPU313 |
| Brand | GE Fanuc |
| Origin | USA |
| Weight | 0.38 kg |
| Dimensions | 132 mm x 36 mm x 100 mm |
| Operating Temp | 0 to 60 deg C |
| Power Consumption | 430 mA at 5 VDC |
| Processor Type | 80186 |
| Processor Speed | 12 MHz |
| User Memory | 12K Bytes |
| Discrete I/O Capacity | 512 Points Max |
| Analog I/O Capacity | 128 Inputs, 64 Outputs Max |
| Maximum Base Racks | 4 (1 CPU Baseplate + 3 Expansion/Remote Baseplates) |
Industrial Network and Backplane Bus Performance
The module interfaces directly with the proprietary Series 90-30 parallel backplane bus architecture, optimizing internal data transfer velocity and clock synchronization between peripheral discrete and analog I/O modules. Deterministic communications across the control network rely on dedicated timing mechanisms driven by the internal 12 MHz processing architecture. This structural setup limits backplane bus propagation delay, ensuring sequential instruction solution speeds execute consistently regardless of the overall I/O density scaling. The embedded system configuration parameters enforce strict network frame pacing to guarantee uninterrupted memory updates across all linked expansion racks.
Frequently Asked Questions
Q: Does the IC693CPU313 module support hot-swap capabilities within the baseplate?
A: No. The Series 90-30 backplane architecture does not feature power-limiting circuits for hot-swapping. Power to the rack baseplate must be fully isolated before inserting or removing the CPU module to prevent structural damage to the backplane contacts and the internal logic chips.
Q: How is the volatile user program memory preserved during a complete system power disruption?
A: User memory retention relies entirely on the backup battery unit located within the power supply module adjacent to the CPU in the baseplate. If the battery is disconnected or falls below its critical threshold voltage, the internal RAM contents will clear upon power loss.
Field Installation Guidelines
- Ensure the primary rack power source is switched off prior to mounting the module into the designated slot 1 of the Series 90-30 baseplate.
- Align the circuit board edge connector carefully with the backplane slot guides and press the module firmly downward until the top and bottom retention hooks click into place.
- Connect the chassis ground terminal of the baseplate to the local copper grounding bar using a minimum of 4 mm squared (11 AWG) low-impedance conductor.
- Route all serial communication cables through dedicated, isolated wireways separated from high-voltage AC lines to minimize electromagnetic interference on the logic circuit.
Return policy
We aim to provide reliable products and a smooth purchasing experience. If there is a problem with your order, please contact us and we will assist according to our Refund Policy.
Shipping
We provide international shipping options to meet different delivery requirements. Please review details regarding methods and timelines in our Shipping Policy.
Warranty
We provide a 12-month warranty for all products, subject to normal use and proper installation.
You may also like
Product Guide
What is an Interposing Relay in a PLC System?
What is an Interposing Relay in a PLC System?
Rockwell CompactLogix 5380 Controller: Advancing Smart Manufacturing with Precision and Connectivity
Rockwell CompactLogix 5380 Controller: Advancing Smart Manufacturing with Precision and Connectivity