Honeywell
TC-IAH161 Honeywell High Level Analog Module
Manufacturer: Honeywell
Product No.: TC-IAH161
Product Type: High Level Analog Module
Product Origin: USA
Payment:T/T, Western Union
Weight: 400g
Shipping port: Xiamen
Warranty: 12 months
Product Overview
The TC-IAH161 (Part Number: TC-IAH161) is a high-density Series C Analog Input module designed for the Honeywell Experion PKS environment. It provides 16 isolated channels capable of interfacing with standard voltage and current signals from field transmitters. Engineered for precision and industrial resilience, the module delivers 16-bit resolution across all input ranges, ensuring high-fidelity data acquisition for critical process loops.
With a 250 ms publish rate, the TC-IAH161 is ideal for standard process monitoring requiring deterministic data updates. Integrated signal conditioning and RFI immunity maintain signal integrity even in electrically noisy industrial environments.
Technical Specifications
| Feature | Specification |
|---|---|
| Model Identification | TC-IAH161 |
| Channel Count | 16 Non-isolated Inputs |
| Voltage Input Ranges | ±10.25 VDC, 0–10.25 VDC, 0–5.125 VDC |
| Current Input Range | 0–20.5 mA (internal 249 Ω precision resistor) |
| A/D Resolution | 16 bits |
| Data Update Rate | 250 ms (Publish Rate) |
| Input Impedance (Voltage) | >1.0 MΩ |
| Input Impedance (Current) | 249 Ω nominal |
| Frequency Response | 20 Hz (-3 dB bandwidth) |
| RFI Protection | <2.0% error at 10 V/m (27–1000 MHz) |
| Thermal Dissipation | 4.1 W maximum |
| Galvanic Isolation | 2550 VDC for 1 second (User-to-System) |
| Required Interface | TC-TBCH 36-position terminal block |
Application Scenarios
-
Interfacing with 4–20 mA pressure and flow transmitters in DCS systems
-
Monitoring voltage-based sensors in power distribution applications
-
General-purpose analog data logging for Series C I/O subsystems
Frequently Asked Questions (FAQ)
Q: Does the TC-IAH161 require an external resistor for current loops?
A: No. The module includes an internal 249 Ω precision resistor for current-to-voltage conversion, simplifying wiring for 0–20 mA or 4–20 mA signals.
Q: Which terminal block is compatible with this module?
A: The TC-IAH161 is designed to work with the TC-TBCH 36-position terminal block for secure field terminations.
Return policy
We aim to provide reliable products and a smooth purchasing experience. If there is a problem with your order, please contact us and we will assist according to our Refund Policy.
Shipping
We provide international shipping options to meet different delivery requirements. Please review details regarding methods and timelines in our Shipping Policy.
Warranty
We provide a 12-month warranty for all products, subject to normal use and proper installation.
You may also like
Product Guide
What is an Interposing Relay in a PLC System?
What is an Interposing Relay in a PLC System?
Rockwell CompactLogix 5380 Controller: Advancing Smart Manufacturing with Precision and Connectivity
Rockwell CompactLogix 5380 Controller: Advancing Smart Manufacturing with Precision and Connectivity