Yokogawa
Yokogawa F3AD04-0N FA-M3 Series A/D Input Module
Manufacturer: Yokogawa
Product No.: F3AD04-0N
Product Type: Analog Input
Product Origin: Japan,Singapore
Payment:T/T, Western Union
Weight: 800g
Shipping port: Xiamen
Warranty: 12 months
Product Overview
The Yokogawa F3AD04-0N is a 4-channel analog-to-digital (A/D) input module for the FA-M3 series. It converts analog voltage signals from sensors and transmitters into digital data with 50 μs conversion speed per point. Supporting multiple input ranges (0-5V, 1-5V, -10 to +10V DC) with differential inputs and 2 MΩ input impedance, it delivers high-accuracy measurement for process control applications.
Key Specifications
- Number of Inputs: 4 differential channels
- Input Signal Ranges: 0 to 5V DC, 1 to 5V DC, -10 to +10V DC
- Conversion Speed: 50 μs per point
- Input Impedance: 2 MΩ
- Common-Mode Voltage: ±6V DC max
- Resolution: 16-bit A/D conversion
- Accuracy: ±0.1% of full scale
- Isolation: Channel-to-system isolation
- Power Consumption: 1.2 W
- Scaling Feature: User-configurable per channel
- CPU Failure Output: Selectable hold or preset per channel
- Weight: 200 g
Compatibility & Applications
Compatible with all FA-M3 CPU modules and base units. Ideal for pressure transmitter monitoring, flow sensor input, level measurement, voltage signal acquisition, and general process analog input applications requiring fast, accurate A/D conversion.
FAQ
- Q: What is the conversion speed? A: 50 μs per point, enabling 200 μs total scan time for all 4 channels.
- Q: Can I mix input ranges on the same module? A: Yes, each channel can be independently configured for 0-5V, 1-5V, or ±10V ranges.
- Q: Does it support 4-20 mA current inputs? A: F3AD04-0N is voltage input only. For 4-20 mA, use F3AD08-1V or install external 250Ω precision resistors.
- Q: What happens if the CPU fails? A: Each channel can be set to either hold the last value or go to a preset safe value during CPU failure.
Installation Guide
- Power off the FA-M3 system.
- Insert F3AD04-0N into any available I/O slot.
- Connect analog signal sources to the terminal block observing polarity.
- Configure input ranges and scaling factors via WideField3 I/O configuration.
- Set CPU failure response (hold/preset) for each channel as required by your safety strategy.
- Restore power and verify analog values match expected sensor readings.
Selection Tips
- Use F3AD04-0N for 4-channel voltage input applications with fast 50 μs conversion.
- For 8-channel applications, consider F3AD08-1V or F3AD08-5R.
- For current input (4-20 mA), select F3AD08-1V or use voltage modules with external resistors.
- Verify signal source impedance is compatible with the 2 MΩ module input impedance.
Return policy
We aim to provide reliable products and a smooth purchasing experience. If there is a problem with your order, please contact us and we will assist according to our Refund Policy.
Shipping
We provide international shipping options to meet different delivery requirements. Please review details regarding methods and timelines in our Shipping Policy.
Warranty
We provide a 12-month warranty for all products, subject to normal use and proper installation.