Product Overview

The Yokogawa F3YD32-1P is a 32-point transistor output module for the FA-M3 series, providing high-density sink-type outputs for industrial control. With 12-24V DC operation and 0.1A per point, it drives solenoid valves, small relays, and indicator lamps in a compact single-slot package. Photocoupler isolation ensures noise immunity, while fast switching response supports high-speed production applications.

Key Specifications

  • Output Type: Transistor (sink type)
  • Number of Outputs: 32 points
  • Rated Load Voltage: 12 to 24V DC
  • Maximum Load Current: 0.1A per point
  • Isolation: Photocoupler isolation
  • Response Time: 1 ms max (OFF→ON and ON→OFF)
  • Current Consumption: Powered via FA-M3 backplane
  • External Power Supply: 12-24V DC required
  • Operating Temperature: 0 to 55°C
  • Weight: 150 g

Compatibility & Applications

Compatible with all FA-M3 base modules and CPU units. Ideal for solenoid valve manifolds, LED indicator panels, small relay driving, pneumatic valve control, and high-density output applications in assembly, packaging, and material handling systems.

FAQ

  • Q: What is the maximum current per point? A: 0.1A per point. For higher current (1A), use F3YD08-6A (8-point module).
  • Q: Can I drive AC loads? A: No, F3YD32-1P is DC only. For AC loads, use F3YC08-0C relay output module.
  • Q: Does it have short-circuit protection? A: Yes, the module includes output protection circuitry.
  • Q: What connector type is used? A: The module uses a 40-pin connector for high-density wiring.

Installation Guide

  1. Power off the FA-M3 system and external 24V supply.
  2. Insert F3YD32-1P into any available I/O slot.
  3. Connect 40-pin ribbon cable or pre-wired harness to the module.
  4. Apply external 12-24V DC power to the module power input.
  5. Restore power and test each output channel via ladder logic.
  6. Verify output LEDs illuminate correctly for each activated channel.

Selection Tips

  • Choose F3YD32-1P for 32-point transistor output density at 0.1A per point.
  • For 64-point maximum density, upgrade to F3YD64-1P.
  • For 1A high-current outputs, use F3YD08-6A (8 points) instead.
  • Calculate total external power supply requirements: module power + sum of all load currents.