Yokogawa
Yokogawa FA-M3 Series F3YD08-6A Transistor Output Module (1A) 8-Point
Manufacturer: Yokogawa
Product No.: F3YD08-6A
Product Type: Transistor Output
Product Origin: Japan,Singapore
Payment:T/T, Western Union
Weight: 800g
Shipping port: Xiamen
Warranty: 12 months
Product Overview
The Yokogawa F3YD08-6A is an 8-point sink-type transistor output module for the FA-M3 series, delivering 1A per point at 12-24V DC. Unlike standard 0.1A modules, this high-current output module can directly drive larger solenoid valves, small DC contactors, and higher-power indicators without external relays. Photocoupler isolation and compact single-slot design make it ideal for power-dense output applications.
Key Specifications
- Output Type: Transistor (sink type, NPN)
- Number of Outputs: 8 points
- Rated Voltage: 12 to 24V DC
- Rated Current: 1A per point
- Isolation: Photocoupler isolation
- Response Time: 1 ms max
- ON Voltage: 0.5V DC max
- Off-State Leak Current: 0.1 mA max
- Protection: Short-circuit protector, overheat shutdown
- Current Consumption: Powered via FA-M3 backplane
- External Power Supply: 12-24V DC required
- Weight: 170 g
Compatibility & Applications
Compatible with all FA-M3 base modules and CPUs. Perfect for large solenoid valve control, DC contactor driving, pneumatic cylinder banks, higher-power LED stacks, and applications requiring 1A per output point without external relay expansion.
FAQ
- Q: What makes F3YD08-6A different from F3YD32-1P? A: F3YD08-6A provides 1A per point (8 points), while F3YD32-1P provides 0.1A per point (32 points). Choose based on current requirements versus point density needs.
- Q: Can it drive AC loads? A: No, this is a DC-only transistor output module. For AC loads, use F3YC08-0C relay module.
- Q: Is there a source-type version? A: Yes, F3YD08-6B is the source-type (PNP) equivalent.
- Q: What wire gauge should I use? A: Use 1.0-1.5 mm² (17-15 AWG) wire rated for at least 1A continuous per point.
Installation Guide
- Power off the FA-M3 system and external 24V supply.
- Insert F3YD08-6A into any available I/O slot.
- Connect loads to the terminal block observing proper polarity for sink outputs.
- Apply external 12-24V DC power to the module power terminals.
- Restore power and test each output using ladder logic or WideField3.
- Monitor module temperature during full-load operation to ensure adequate ventilation.
Selection Tips
- Select F3YD08-6A when you need 1A per point in an 8-point module.
- For 0.5A per point with 14 outputs, consider F3YD14-5A for higher density.
- For 0.1A high-density applications, F3YD32-1P or F3YD64-1P are more economical per point.
- Always include a 20% current margin and verify wire gauge ratings for 1A continuous operation.
Return policy
We aim to provide reliable products and a smooth purchasing experience. If there is a problem with your order, please contact us and we will assist according to our Refund Policy.
Shipping
We provide international shipping options to meet different delivery requirements. Please review details regarding methods and timelines in our Shipping Policy.
Warranty
We provide a 12-month warranty for all products, subject to normal use and proper installation.
You may also like
Product Guide
Mitigating SCADA Performance Drops During Shift Transitions
Mitigating SCADA Performance Drops During Shift Transitions
Optimizing SCADA Performance: Why Remote Clients Experience Lag
Optimizing SCADA Performance: Why Remote Clients Experience Lag